3.2.2 Mounting input/output terminal module

Mount the input/output terminal module on the panel; observing the following method.

(Note) To avoid the effect of noise generated from external units, mount the I/O terminal module

mounting plate on the panel for continuity at the mounting surface and connect the panel
to the same ground as the analyzer main unit.

Note) How to ground analyzer main unit and I/O terminal module

* Don’t separate the analyzer and I/O terminal module, and be sure to
ground them together.

Mount the analyzer and I/O terminal module on the
same panel.

Bring I/O terminal module sheet metal and
panel into continuity at ///// portion.

To avoid the effect of noises, etc. from external units, it is
recommended to ground them by the procedure described below.

Bring analyzer main unit and panel into continuity
at ///// portion or rail mounting portion.
(No grounding is required at the power terminal).

Ground the panel casing.

External dimensions

Mounting dimensions

Mounting method

Terminal

Screwed to panel

Panel plate

To analyzer rear panel

Connection cable

4.5 mounting hole (

×

6 places)

M4 screw (

×

6 places)

Rectangular hole

302

142142

154

150

150

316

164