SilentKnight VisorAlarm ARLY Interface User Manual
Page 10

VISOR ALARM – ARLY Configuration
II - 5
Doc.DM359-I
Rev.2.0
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION,
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to specific values or not used at all as
indicated below.
Program feature or
option
Permitted in UL 864?
(Y/N)
Possible settings
Settings permitted in UL 864
2.1d)
N
0-3000 seconds
1-60 seconds
2.1f) N
Alarm-signals,
Trouble-signals,
None-signals
Alarm-signals,
Trouble-signals
2.4 i)
N
0-90 seconds
1-60 seconds
2.4 j)
N
1-9
1
2.4 p)
N
0-90 seconds
1-60 seconds
2.6 a)
N
Disabled,
Ac-loss,
Low-battery
AC loss,
Low battery
2.9 h)
N
0-90 seconds
1-60 seconds
2.9 i)
N
1-9
1
2.9 j)
N
3-9
3
2.9 n)
N
0-90 seconds
1-60 seconds
2.9 o)
N
1-9
1