VISOR ALARM – ARLY Configuration
II - 67
Doc.DM359-I
Rev.2.0
ARLY-1 Cfg>USER-DEFINED-EVENTS AC-LOSS 301
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO USER-DEFINED-EVENTS AC-LOSS <code>
t) USER-DEFINED-EVENTS LOW-BATTERY
Permits you to configure the event code to be sent in the alarm generated by the VisorALARM when
a low battery condition at the UPS (voltage between
10.2V and 11.5V
) is detected through the
activation (by the UPS) of the VisorALARM’s general purpose input configured for this purpose. By
default the alarm code is 302 (low system battery).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS LOW-BATTERY <code>
ARLY-1 Cfg>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS LOW-BATTERY 302
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO USER-DEFINED-EVENTS LOW-BATTERY <code>
u) USER-DEFINED-EVENTS LOG-CLEAR
Permits you to configure the event code to be sent in the alarm generated by the VisorALARM
whenever the SRAM events log is cleared by an user (execution of command “log clear” in the ARLY
interface menu) or by the VisorALARM itself (as a consequence of an integrity error detection at
SRAM events log). By default the alarm code is 621 (event log reset).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS LOG-CLEAR <code>
ARLY-1 Cfg>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS LOG-CLEAR 621
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO USER-DEFINED-EVENTS LOG-CLEAR <code>
v) USER-DEFINED-EVENTS LOG-50LOAD
Permits you to configure the event code to be sent in the alarm generated by the VisorALARM when
the SRAM event log is detected to have loaded to 50 % of its current total capacity. By default the
alarm code is 622 (event log 50% full).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS LOG-50LOAD <code>
ARLY-1 Cfg>
Example: