SilentKnight VisorAlarm ARLY Interface User Manual
Page 66

VISOR ALARM – ARLY Configuration
II - 61
Doc.DM359-I
Rev.2.0
ARLY-1 Cfg>NO USER-DEFINED-EVENTS MIP-REGISTRATION <code>
b) USER-DEFINED-EVENTS MIP-LOSS
Permits you to configure the event code to be sent in the generated alarm when contact with an
mIP/IPDACT is lost, as packets indicating the mIP/IPDACT is active are no longer being received.
Default value for this parameter is 350 (Communication trouble event).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS MIP-LOSS <code>
ARLY-1 Cfg>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS MIP-LOSS 351
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command:
ARLY-1 Cfg>NO USER-DEFINED-EVENTS MIP-LOSS <code>
c) USER-DEFINED-EVENTS NETWORK-FAILURE
Permits you to configure the event code to be sent in the generated alarm when an IP connectivity
problem is detected in the VisorALARM. Default value for this parameter is 356 (Loss of central
polling event).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS NETWORK-FAILURE <code>
ARLY-1 Cfg>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS NETWORK-FAILURE 357
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command:
ARLY-1 Cfg>NO USER-DEFINED-EVENTS NETWORK-FAILURE <code>
d) USER-DEFINED-EVENTS COMMUNICATION-FAILURE
Permits you to configure the event code to be sent in the alarm generated by the backup
VisorALARM when an IP connectivity problem between the mIP/IPDACT and the main
VisorALARM is detected. Detection is based on the fact that the backup VisorALARM receives
polls from an mIP/IPDACT which has switched to backup, but has not detected that the main has
failed. Default value for this parameter is 394.
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS COMMUNICATION-FAILURE <code>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS COMMUNICATION-FAILURE 394
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.