2. Fire System Installations complying with UL864

Configure the configuration profiles for all the mIP devices so they comply with the requirements
established by the UL. This states that automatic switching to the backup receiver must occur in a
maximum time of 30 seconds. We strongly recommend you set the ‘keep-alive-timer’, keep-alive-
retries’ and ‘keep-alive-retries-timer’, so they comply with the following formula:

keep-alive-timer + (keep-alive-retries * keep-alive-retries-timer) < 25


Configure the configuration profiles for all the mIP devices so the “MIP Console Password” parameter
contains the access password for the mIP devices.

Add a password to the VisorALARM receiver. This password is used both for connections via the
console as well as via telnet. Make sure the administration staff at the Central Station both know it
and keep it in a safe place for future use.

Configure the ‘link-test-timer’ parameter for both the main receiver and the backup to a value between
60 and 200 seconds.