VISOR ALARM – ARLY Configuration

II - 42

Doc.DM359-I

Rev.2.0

Syntax:

ARLY-1 Cfg>MIP accnt CALLBACK-PHONE telephone_number

telephone_number

Telephone number dialed by the control panel to execute bi-
directional in call-back mode.


Example:

ARLY-1 Cfg>MIP 101234 CALLBACK-PHONE 918076123
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command:

ARLY-1 Cfg>NO MIP accnt CALLBACK-PHONE telephone_number

n) MIP accnt BCK-KEEP-ALIVE-TIMER
This parameter is the same as the keep-alive-timer however it is applied to the backup
VisorALARM.

Syntax:

ARLY-1 Cfg>MIP accnt BCK-KEEP-ALIVE-TIMER time

Time

Time in seconds between keep-alive frames. Admits values between 0
and 90.


Example:

ARLY-1 Cfg>MIP 101234 BCK-KEEP-ALIVE-TIMER 30
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO MIP accnt BCK-KEEP-ALIVE-TIMER time

If you use a value of zero for the “bck-keep-alive-timer parameter”, the mIP/IPDACT
will not send supervision trafic to the receiver and the VisorALARM will not be able to
access the device for remote configuration.

o) MIP accnt BCK-KEEP-ALIVE-RETRIES
This parameter is the same as the keep-alive-retries however it is applied to the backup
VisorALARM.

Syntax:

ARLY-1 Cfg>MIP accnt BCK-KEEP-ALIVE-RETRIES num_times

num_times

Number of times keep-alive frames are sent in situations where
responses are not received. Admits values between 1 and 9.