SilentKnight VisorAlarm ARLY Interface User Manual
Page 14

VISOR ALARM – ARLY Configuration
II - 9
Doc.DM359-I
Rev.2.0
ARLY-1 Cfg>NO ALARM-RECEIVER PROTOCOL protocol
b) ALARM-RECEIVER RECEIVER-ID
Configures the VisorALARM receiver identifier so it can be identified in the Automation Sw.
Admits a maximum of two digits (0 to 9). Default value is 1.
Syntax:
ARLY-1 Cfg>ALARM-RECEIVER RECEIVER-ID identifier
Example:
ARLY-1 Cfg>ALARM-RECEIVER RECEIVER-ID 8
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command:
ARLY-1 Cfg>NO ALARM-RECEIVER RECEIVER-ID identifier
c) ALARM-RECEIVER LINE-ID
Configures the VisorALARM line identifier so it can be identified in the Automation Sw.
Admits a maximum of three digits (0 to 9). Default value is 01.
Syntax:
ARLY-1 Cfg>ALARM-RECEIVER LINE-ID identifier
Example:
ARLY-1 Cfg>ALARM-RECEIVER LINE-ID 12
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command:
ARLY-1 Cfg>NO ALARM-RECEIVER LINE-ID identifier
d) ALARM-RECEIVER LINK-TEST-TIMER
Configures the interval through which the alarms receiver connection is checked – Automation Sw.
Exchanging a particular type of frame carries out this check. If the exchange is satisfactory, the
ARLY interface is considered active (UP) and the WAN1 LED lights up in green.
Admits values between 0 and 3000 seconds. If you configure this parameter with a 0 value, the said
exchange will not take place and the interface will be considered up. Default value is 0.
Syntax:
ARLY-1 Cfg>ALARM-RECEIVER LINK-TEST-TIMER value
Example:
ARLY-1 Cfg>ALARM-RECEIVER LINK-TEST-TIMER 180
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command:
ARLY-1 Cfg>NO ALARM-RECEIVER LINK-TEST-TIMER value
e) ALARM-RECEIVER PARAMETERS
Admits a string of parameters depending on the type of receiver emulated.
In cases where the emulated receiver is Sur-Gard, you can configure:
r
Type of emulated receiver: 0 MLR2000/MLR2E, 1 DLR-2. Default is 0.