VISOR ALARM – ARLY Configuration

II - 64

Doc.DM359-I

Rev.2.0

ARLY-1 Cfg>NO USER-DEFINED-EVENTS INPUT-CHANGED <code>


In the IP Module hardware, the input has three possible states:

ƒ

No alarm, where the mIP/IPDACT detects a 1000 ohms resistance at its input.

ƒ

Short-circuit in the input, which generates and alarm in the mIP/IPDACT whose default code

has a value of 110 (fire alarm).

ƒ

Open circuit in the input, so the mIP/IPDACT considers there has been sabotage or sensor

failure and sends an alarm. This code is set through the INPUT-SENSOR-TROUBLE event

k) USER-DEFINED-EVENTS INPUT-SENSOR-TROUBLE
This permits you to configure the event code sent in the alarm generated by the main VisorALARM
when it receives an open circuit in the input alarm from the mIP/IPDACT. The mIP/IPDACT
considers either sabotage has occurred or the sensor has failed. The default code for this alarm is 380
(Sensor trouble).Syntax:

ARLY-1 Cfg>USER-DEFINED-EVENTS INPUT-SENSOR-TROUBLE <code>
ARLY-1 Cfg>

Example:

ARLY-1 Cfg>USER-DEFINED-EVENTS INPUT-SENSOR-TROUBLE 390
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO USER-DEFINED-EVENTS INPUT-SENSOR-TROUBLE <code>

l) USER-DEFINED-EVENTS-TAMPER
The IP Module hardware has a tamper input to detect the opening of the alarms panel. Under normal
circumstances, the input must be short-circuited. When this detects an open circuit, the module
considers that the panel has been opened and sends an alarm to the mIP/IPDACT with default code
383 (Sensor Tamper).
Syntax:

ARLY-1 Cfg>USER-DEFINED-EVENTS TAMPER <code>
ARLY-1 Cfg>

Example:

ARLY-1 Cfg>USER-DEFINED-EVENTS TAMPER 384
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO USER-DEFINED-EVENTS TAMPER <code>

m) USER-DEFINED-EVENTS PSTN-FAILURE
The IP Module hardware supervises the telephone line detecting possible failures on this. If a failure
is detected, the IP Module sends an alarm which, by default, the VisorALARM interprets with the
CONTACT-ID 351 code (Fail Telco-1).
Syntax:

ARLY-1 Cfg>USER-DEFINED-EVENTS PSTN-FAILURE <code>

Example:

ARLY-1 Cfg>USER-DEFINED-EVENTS PSTN-FAILURE 352
ARLY-1 Cfg>