Description, Io-conf – SilentKnight VisorAlarm ARLY Interface User Manual

Page 29

Advertising
background image

VISOR ALARM – ARLY Configuration

II - 24

Doc.DM359-I

Rev.2.0

ARLY-1 Cfg>NO CFG-PATTERN n MNT-PASSWORD clave

2.5. DESCRIPTION

Permits the user to add a text which will appear on displaying the device configuration. The aim of
this command is to facilitate the user, reading, compression and modification of the interface
configuration. Admits up to 63 characters including blank spaces. To eliminate the description, use
the NO DESCRIPTION command. Default is no description configured.
Syntax:

ARLY-1 Cfg>DESCRIPTION text

Example:

ARLY-1 Cfg>DESCRIPTION Interface emulating ARC is Sur-Gard
ARLY-1 Cfg>

2.6. IO-CONF

Permits the user to configure the general purpose output and each of the two inputs of a VA-UD
expansion board for signaling the selected events from a given list of possibilities.
Syntax:

ARLY-1 Cfg>io-conf ?
input1 Configure the general purpose input 1
input2 Configure the general purpose input 2
output Configure the general purpose output

a) IO-CONF INPUTx
Configures each of the two inputs (input1, input2) as disabled (no signal will be monitored at the
input) or for indicating ac-loss or low-battery conditions at the UPS power system (Uninterruptible
power supply).
Syntax:

ARLY-1 Cfg>io-conf <inputX> <condition>
disabled Disable input
ac-loss Signal AC loss
low-battery Signal low system battery

inputX

Selected general purpose input (input1 / input2).

condition

Condition to be signaled by the selected input

Disabled. No signal monitored.
AC-loss. AC loss (<

10.2V)

at the UPS power system.

Low-battery. Low battery (

Batt 10.2-11.5V

) at the UPS

power system.


Example:

ARLY-1 Cfg>io-conf input1 ac-loss
ARLY-1 Cfg>io-conf input2 low-battery
ARLY-1 Cfg>


The default configuration sets input1 to signal AC-loss condition and input2 to indicate Low-battery
condition in the UPS.