Description, Io-conf – SilentKnight VisorAlarm ARLY Interface User Manual
Page 29

VISOR ALARM – ARLY Configuration
II - 24
Doc.DM359-I
Rev.2.0
ARLY-1 Cfg>NO CFG-PATTERN n MNT-PASSWORD clave
2.5. DESCRIPTION
Permits the user to add a text which will appear on displaying the device configuration. The aim of
this command is to facilitate the user, reading, compression and modification of the interface
configuration. Admits up to 63 characters including blank spaces. To eliminate the description, use
the NO DESCRIPTION command. Default is no description configured.
Syntax:
ARLY-1 Cfg>DESCRIPTION text
Example:
ARLY-1 Cfg>DESCRIPTION Interface emulating ARC is Sur-Gard
ARLY-1 Cfg>
2.6. IO-CONF
Permits the user to configure the general purpose output and each of the two inputs of a VA-UD
expansion board for signaling the selected events from a given list of possibilities.
Syntax:
ARLY-1 Cfg>io-conf ?
input1 Configure the general purpose input 1
input2 Configure the general purpose input 2
output Configure the general purpose output
a) IO-CONF INPUTx
Configures each of the two inputs (input1, input2) as disabled (no signal will be monitored at the
input) or for indicating ac-loss or low-battery conditions at the UPS power system (Uninterruptible
power supply).
Syntax:
ARLY-1 Cfg>io-conf <inputX> <condition>
disabled Disable input
ac-loss Signal AC loss
low-battery Signal low system battery
inputX
Selected general purpose input (input1 / input2).
condition
Condition to be signaled by the selected input
• Disabled. No signal monitored.
• AC-loss. AC loss (<
10.2V)
at the UPS power system.
• Low-battery. Low battery (
Batt 10.2-11.5V
) at the UPS
power system.
Example:
ARLY-1 Cfg>io-conf input1 ac-loss
ARLY-1 Cfg>io-conf input2 low-battery
ARLY-1 Cfg>
The default configuration sets input1 to signal AC-loss condition and input2 to indicate Low-battery
condition in the UPS.