VISOR ALARM – ARLY Configuration

II - 22

Doc.DM359-I

Rev.2.0

ARLY-1 Cfg>CFG-PATTERN 10 BCK-KEEP-ALIVE-TIMER 30
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO CFG-PATTERN n BCK-KEEP-ALIVE-TIMER time

If you use a value of zero for the “bck-keep-alive-timer parameter”, the mIP/IPDACT
will not send supervision trafic to the receiver and the VisorALARM will not be able to
access the device for remote configuration.

q) CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES
This parameter is the same as the keep-alive-retries however it is applied to the backup
VisorALARM.
Syntax:

ARLY-1 Cfg>CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES num_times

num_times

Number of times keep-alive frames are sent in situations where
responses are not received. Admits values between 1 and 9.


Example:

ARLY-1 Cfg>CFG-PATTERN 10 BCK-KEEP-ALIVE-TIMER 30
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES time

r) CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES -TIME
This parameter is the same as the keep-alive-retries-time however it is applied to the
backup VisorALARM.
Syntax:

ARLY-1 Cfg>CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES-TIMER time

Time

Time in seconds between keep-alive frames when a possible
connectivity failure has been detected. Admits values between 3 and
9.


Example:

ARLY-1 Cfg>CFG-PATTERN 10 BCK-KEEP-ALIVE-RETRIES-TIMER 1
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES-TIMER time

s) CFG-PATTERN n LOCAL-EVENTS-ZONE
This parameter defines the base number for the zone field that will be appear in all the events
generated by a mIP/IPDACT that does not come from the Alarm Panel. This parameter is not sent to