SilentKnight VisorAlarm ARLY Interface User Manual
Page 27

VISOR ALARM – ARLY Configuration
II - 22
Doc.DM359-I
Rev.2.0
ARLY-1 Cfg>CFG-PATTERN 10 BCK-KEEP-ALIVE-TIMER 30
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO CFG-PATTERN n BCK-KEEP-ALIVE-TIMER time
If you use a value of zero for the “bck-keep-alive-timer parameter”, the mIP/IPDACT
will not send supervision trafic to the receiver and the VisorALARM will not be able to
access the device for remote configuration.
q) CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES
This parameter is the same as the keep-alive-retries however it is applied to the backup
VisorALARM.
Syntax:
ARLY-1 Cfg>CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES num_times
num_times
Number of times keep-alive frames are sent in situations where
responses are not received. Admits values between 1 and 9.
Example:
ARLY-1 Cfg>CFG-PATTERN 10 BCK-KEEP-ALIVE-TIMER 30
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES time
r) CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES -TIME
This parameter is the same as the keep-alive-retries-time however it is applied to the
backup VisorALARM.
Syntax:
ARLY-1 Cfg>CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES-TIMER time
Time
Time in seconds between keep-alive frames when a possible
connectivity failure has been detected. Admits values between 3 and
9.
Example:
ARLY-1 Cfg>CFG-PATTERN 10 BCK-KEEP-ALIVE-RETRIES-TIMER 1
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO CFG-PATTERN n BCK-KEEP-ALIVE-RETRIES-TIMER time
s) CFG-PATTERN n LOCAL-EVENTS-ZONE
This parameter defines the base number for the zone field that will be appear in all the events
generated by a mIP/IPDACT that does not come from the Alarm Panel. This parameter is not sent to