Else

'C!/C command sequence complete

Move

(Temp_Meas(X),1,Temp_Tmp(X),1)

'Copy measurements to SDI_Val(10)

cmd(X) = "C!"

'Start next measurement with "C!"

IndDone(X) = -1

EndIf

Next

X

'Summarize Measurement Event Success

For

X = 1

To

4

GroupDone = GroupDone + IndDone(X)

Next

X

'Stop current measurement event, reset controls

If

GroupDone = -4

Then

RunSDI12 = False
GroupDone = 0

For

X = 1

To

4

IndDone(X) = 0
Retry(X) = 0

Next

X

Else

GroupDone = 0

EndIf

EndIf

'End of measurement sequence

NextScan

EndProg

 

CRBasic Example 34. Using SDI12Sensor() Command 

'Program to simulate 4 SDI-12 sensors. Can be used to produce measurements to test

'CRBasic example Using Alternate Concurrent Command (aC)

(p. 181).

Public

Temp(4)

DataTable

(Temp,True,0)

DataInterval

(0,5,Min,10)

Sample

(4,Temp(),FP2)

EndTable

BeginProg

Scan

(5,Sec,0,0)

PanelTemp

(Temp(1),250)

Temp(2) = Temp(1) + 5
Temp(3) = Temp(1) + 10
Temp(4) = Temp(1) + 15

CallTable

Temp

NextScan