2 measurement rate: 101 to 600 hz – Campbell Scientific CR1000 Measurement and Control System User Manual

Page 233

Advertising
background image

Section 7. Installation

233

 

BeginProg

Scan

(1,Sec,0,0)

'<<<<Measurement rate is determined by Interval and Units

VoltSe

(FastSE(),1,mV2_5,1,False,100,250,1.0,0)

CallTable

FastSETable

NextScan

EndProg

By modifying the

Interval

,

Units

,

and Buffers

arguments, VoltSE() can be

executed at 100 Hz at 100% duty cycle. The following program measures 16
analog input channels at 100 Hz.

Table 34. CRBasic EXAMPLE. Measuring VoltSE() at 100 Hz

PipeLineMode

'<<<<Pipeline mode ensures precise timing of measurements.

Public

FastSE(16)

DataTable

(FastSETable,1,-1)

Sample

(16,FastSE(),FP2)

EndTable

BeginProg

Scan

(10,mSec,10,0)

'<<<<Measurement rate is determined by Interval, Units, and Buffers

VoltSe

(FastSE(),16,mV2_5,1,False,100,250,1.0,0)

CallTable

FastSETable

NextScan

EndProg

7.8.12.2 Measurement Rate: 101 to 600 Hz

To measure at rates between 100 and 600 Hz, the SubScan() / NextSubScan
instruction pair is added. Measurements over 100 Hz do not do not have 100%
duty cycle, but are accomplished through measurement bursts. Each burst lasts
for some fraction of the scan interval. During the remainder of the scan interval,
the CR1000 processor catches up on overhead tasks and processes data stored in
the buffers. For example, the CR1000 can be programmed to measure VoltSE()
on 8 channels at 200 Hz with a 95% duty cycle as follows:

Table 35. Measuring VoltSE() at 200 Hz

PipeLineMode

'<<<<Pipeline mode ensures precise timing of measurements.

Public

BurstSE(8)

DataTable

(BurstSETable,1,-1)

Sample

(8,BurstSE(),FP2)

EndTable

BeginProg

Scan

(1,Sec,10,0)

'<<<<Buffers added

SubScan

(5,mSec,190)

'<<<<Interval, Units, and Count determine speed and number of measurements

VoltSe

(BurstSE(),8,mV2_5,1,False,100,250,1.0,0)

CallTable

BurstSETable

NextSubScan

NextScan

EndProg