Section 7. Installation

186 

 

 

Example:

Probe: Water Content

Power Usage:

• Quiescent: 0.25 mA
• Measurement: 120 mA
• Measurement Time: 15 s
• Active: 66 mA
• Timeout: 15 s

Probes 1, 2, 3, and 4 are connected to SDI-12 / Control Port 1.

The time line in table Example Power Usage Profile for a Network of SDI-12
Probes

(p. 186)

shows a 35-second power-usage profile example.

For most applications, total power usage of 318 mA for 15 seconds is not
excessive, but if 16 probes were wired to the same SDI-12 port, the resulting
power draw would be excessive. Spreading sensors over several SDI-12 terminals
will help reduce power consumption.

Table 28. Example Power Usage Profile for a Network of SDI-12 Probes

Sec Command

All

Probes

Awake

Time

Out

Expires

1 mA

2 mA

3 mA

4 mA

Total

mA

1

1M!

Yes 120

66 66 66

318

2

120 66 66 66 318

• • • • •

• • • • •

• • • • •

14

120 66 66 66 318

15

Yes 120 66 66 66 318

16

1D0!

Yes 66 66 66 66

264

17

66 66 66 66 264

• • • • •

• • • • •

• • • • •

29

66 66 66 66 264

30

Yes 66 66 66 66 264

31

0.25 0.25 0.25 0.25 1

• • • • •

• • • • •

• • • • •

35

0.25 0.25 0.25 0.25 1

 