Section 4. Quickstart Tutorial

39

 

4.1.3.3.1 Pulses Measured

Figure Pulse Sensor Output Signal Types

(p. 39)

illustrates three pulse sensor output

signal types.

Figure 7: Pulse-sensor output signal types

4.1.3.3.2 Pulse-Input Channels

Table Pulse-Input Channels and Measurements

(p. 39)

lists devices, channels and

options for measuring pulse signals.

Table 2. Pulse-Input Channels and Measurements

Pulse-Input

Channel

Input Type

Data Option

CRBasic

Instruction

P1, P2

High-frequency

Low-level ac

Switch-closure

Counts

Frequency

Run average
of frequency

PulseCount()

C1, C2, C3, C4,

C5, C6, C7, C8

High-frequency

Switch-closure

Low-level ac
(with LLAC4
Low-Level AC
Conversion
Module)

Counts

Frequency

Running
average of
frequency

Interval

Period

State

PulseCount()

TimerIO()

 

4.1.3.3.3 Pulse Sensor Wiring

Wiring a pulse sensor to a CR1000 is straight forward, as shown in figure Pulse-
Input Wiring -- Anemometer Switch

(p. 40).

Pulse sensors have two active wires,

one of which is always ground. Connect the ground wire to a

(ground)