Appendix A. CRBasic Programming Instructions

481

 


-or-

If

[condition 1] Then

[then statements]

ElseIf

[condition 2] Then

[elseif then statements]

Else

[else statements]

EndIf

Scan / ExitScan / ContinueScan / NextScan 
Establishes the program scan rate. ExitScan and ContinueScan are optional.  See 
Faster Measurement Rates

 (p. 231) 

for information on use of Scan() / NextScan in 

burst measurements. 

Syntax 

Scan

(Interval, Units, Option, Count)

[statement block]

ExitScan

[statement block]

ContinueScan

[statement block]

NextScan

Select Case / Case / Case Is / Case Else / EndSelect 
Executes one of several statement blocks depending on the value of an 
expression. CaseElse is optional. Note that EndSelect and EndIf call the same 
function. 

Syntax 

Select Case

testexpression

Case

[expression 1]

[statement block 1]

Case

[expression 2]

[statement block 2]

Case Is

[expression fragment]

Case Else

[statement block 3]

EndSelect

SlowSequence 
Marks the beginning of a section of code that will run concurrently with the main 
program. 

Syntax 

SlowSequence

SubScan / NextSubScan 
Controls a multiplexer or measures some analog inputs at a faster rate than the 
program scan.  See Faster Measurement Rates (p. 231) for information on use of 
SubScan / NextSubScan in burst measurements. 

Syntax 

SubScan

(SubInterval, Units, Count)

[measurements and processing]

NextSubScan