Section 8. Operation

291

 

measurements (B) to be determined during CR1000 self-calibration (maximum of
54 values). These values can be viewed in the Status table, with entries identified
as listed in table Status Table Calibration Entries

(p. 291).

Automatic self-calibration can be overridden with the Calibrate() instruction,
which forces a calibration for each execution, and does not employ any low-pass
filtering on the newly determined G and B values. There are two parameters
associated with the Calibrate() instruction:

CalRange

and

Dest

.

CalRange

determines whether to calibrate only the necessary input ranges for a given
CRBasic program (

CalRange

= 0) or to calibrate all input ranges (

CalRange

≠ 0).

The

Dest

parameter should be of sufficient dimension for all the returned G and B

values, which is a minimum of two for the automatic self-calibration of VoltSE()
including B (offset) for the ±2500 mV input range with first 250 µs integration,
and a maximum of 54 for all possible integration durations and input-voltage
ranges chosen.

An example use of the Calibrate() instruction programmed to calibrate all input
ranges is given as:

'Calibrate(Dest,Range)

Calibrate

(cal(1),true)

where

Dest

is an array of 54 variables, and

Range

≠ 0 to calibrate all input ranges.

Results of this command are listed in the table Calibrate() Instruction Results

(p.

293).

Table 59. Status Table Calibration Entries

Descriptions of Status Table Elements

Status Table

Element

Differential (Diff)

Single-Ended (SE)

Offset or Gain

±mV Input

Range

Integration

CalGain(1)

Gain 5000 250

ms

CalGain(2)

Gain 2500 250

ms

CalGain(3)

Gain

250 250

ms

CalGain(4)

Gain

25

250

ms

CalGain(5)

Gain

7.5

250

ms

CalGain(6)

Gain

2.5

250

ms

CalGain(7)

Gain 5000

60-Hz

Rejection

CalGain(8)

Gain 2500

60-Hz

Rejection

CalGain(9)

Gain

250

60-Hz

Rejection

CalGain(10)

Gain

25 60-Hz

Rejection

CalGain(11)

Gain

7.5 60-Hz

Rejection

CalGain(12)

Gain

2.5 60-Hz

Rejection

CalGain(13)

Gain

5000

50-Hz

Rejection

CalGain(14)

Gain

2500

50-Hz

Rejection

CalGain(15)

Gain

250

50-Hz

Rejection

CalGain(16)

Gain

25 50-Hz

Rejection

CalGain(17)

Gain

7.5 50-Hz

Rejection