Appendix B. Status Table and Settings

529

 

Table 121. Status-Table Fields and Descriptions

Fieldname Description

Variable

Type

Default

Range

Edit?

Info

Type

RevBoard

xxx.yyy
xxx = hardware revision
number; yyy = clock chip
software revision; stored in
FLASH memory.

Integer

Status

StationName1

Sets a name internal to the
CR1000. Stored in flash
memory. Not to be confused
with the station name set in
datalogger support software.
See foot note for limitations.

String

Yes

Config

PakBusAddress2

CR1000 PakBus address.

String

1

1 to 3999

Yes

Config PB

ProgName

Name of current (running)
program.

String

Status

StartTime

Time the program began
running.

Time

Status

RunSignature

Signature of the compiled
binary data structure for the
current program. Value is
independent of comments
added or non-functional
changes to the program.
Often changes with
operating-system changes.

Integer

Status

ProgSignature

Signature of the current
running program file
including comments. Does
not change with operating
system changes.

Integer

Status

Battery

Current value of the battery
voltage. Measurement is
made in the background
calibration.

Float

9.6-16

Vdc

Measure

PanelTemp

Current wiring-panel
temperature. Measurement is
made in the background
calibration.

Float

Measure

WatchdogErrors3

Number of Watchdog errors
that have occurred while
running this program.

Integer 0

0

Yes
Reset by
changing to 0

Error

LithiumBattery4

Current voltage of the
lithium battery. Measurement
is updated in background
calibration.

Float

2.7-3.6

Vdc

Measure