540 

 

 

Table 122. CR1000 Settings

Settings are accessed through the Campbell Scientific Device Configuration Utility (DevConfig) via direct-serial and IP connections, or through
PakBusGraph via most CR1000 supported telecommunications options.

Setting Description

Default

Entry

OS Version

Specifies the version of the operating system currently in the CR1000.

Serial Number

Specifies the CR1000 serial number assigned by the factory when the CR1000 was
calibrated.

Station Name

Specifies a name assigned to this station.

PakBus Address

This setting specifies the PakBus® address for this device. The value for this setting
must be chosen such that the address of the device is unique in the scope of the
datalogger network. Duplication of PakBus® addresses in two or more devices can lead
to failures and unpredictable behavior in the PakBus® network. The following values
are the default addresses of various types of software and devices and should probably
be avoided:

Device

PB Address

LoggerNet

4094

PC400

4093

PC200

4092

Visual Weather 4091

RTDAQ

4090

DevConfig 4089

NL100

678

All other devices 1

1

Security Level 1

Specifies Level 1 Security. Zero disables all security. Range: 0 to 65535. See Security

(p. 70).

0

Security Level 2

Specifies Level 2 Security. Zero disables levels 2 & 3. Range: 0 to 65535. See Security

(p. 70).

0

Security Level 3

Specifies Level 3 Security. Zero disables level 3. Range: 0 to 65535. See Security

(p.

70).

0

UTC Offset

The offset, in seconds, that the CR1000's local time is from UTC. This offset is used in
email and HTML headers, since these protocols require the time stamp to be reflected in
UTC. This offset will also be used by the GPS instruction, NetworkTimeProtocol
instruction, and DaylightSavingTime functions when enabled.

-1 (Disabled)

Is Router

This setting controls whether the CR1000 is configured as a router or as a leaf node. If
the value of this setting is non-zero, the CR1000 is configured to act as a PakBus

®

router. That is, it is able to forward PakBus

®

packets from one port to another. To

perform its routing duties, a CR1000 configured as a router will maintain its own list of
neighbors and send this list to other routers in the PakBus

®

network. It will also obtain

and receive neighbor lists from other routers.
If the value of this setting is zero, the CR1000 is configured to act as a leaf node. In this
configuration, the CR1000 will not be able to forward packets from one port to another
and it will not maintain a list of neighbors. Under this configuration, the CR1000 can
still communicate with other dataloggers and wireless sensors. It cannot, however, be
used as a means of reaching those other dataloggers.

0

PakBus Nodes Allocation

Specifies the amount of memory that the CR1000 allocates for maintaining PakBus

®

routing information. This value represents roughly the maximum number of PakBus

®

nodes that the CR1000 is able to track in its routing tables.

50