Campbell Scientific CR1000 Measurement and Control System User Manual

Page 255

Advertising
background image

Section 7. Installation

255

 

Table 45. PRTCalc() Type-Code-1 Sensor

IEC 60751:2008 (IEC 751), alpha = 0.00385. Now internationally
adopted and written into standards ASTM E1137-04, JIS 1604:1997,
EN 60751 and others. This type code is also used with probes
compliant with older standards DIN43760, BS1904, and others.
(Reference: IEC 60751. ASTM E1137)

Constant Coefficient

e 1.7584810E-05

f -1.1550000E-06

g 1.7909000E+00

h -2.9236300E+00

i 9.1455000E+00

j 2.5581900E+02

 

Table 46. PRTCalc() Type-Code-2 Sensor

US Industrial Standard, alpha = 0.00392 (Reference: Logan
Enterprises)

Constant Coefficient

a 3.9786300E-03

d -2.3452400E-06

e 1.8174740E-05

f -1.1726200E-06

g 1.7043690E+00

h -2.7795010E+00

i 8.8078440E+00

j 2.5129740E+02

 

Table 47. PRTCalc() Type-Code-3 Sensor

US Industrial Standard, alpha = 0.00391 (Reference: OMIL R84
(2003))

Constant Coefficient

a 3.9690000E-03

d -2.3364000E-06

e 1.8089360E-05

f -1.1682000E-06

g 1.7010560E+00

h -2.6953500E+00

Advertising