Electrical System

FUNCTION ENABLE
INTERLOCK –
ENABLE SWITCH
NOT SELECTED
FIRST

2227

1

The requested function will be

ignored.

If the PLATFORM STATION is

active and a platform is configured

as ENABLED and a platform is

detected as attached and a

hydraulic function request is detect

at the platform station before the

function enable signal was

received.

The hydraulic

function

request is no

longer active.

FUNCTION ENABLE
INTERLOCK – NOT
SELECTED IN TIME

2228

1

Turn OFF the functions enabled

indicator at the platform station.

Ignore all function requests from

the platform station while the

FUNCTIONS ENABLED state is

active.

If the PLATFORM STATION is

active and a platform is configured

as ENABLED and a platform is

detected as attached and if a

function request is not received

within the 7 second period from the

time the FUNCTION ENABLE state

is activated.

The function

enable switch

is released.

ENGINE START
PREVENTED –
FUNCTION ENABLE
SWITCH ENGAGED

2229

1

The engine start signal will be

ignored. J2-26 Engage Starter will

be deactivated and inhibited.

When the PLATFORM STATION is

active and the engine start signal is

detected at the platform and the

UGM detects the function enable

switch is engaged.

The function

enable switch

is released.

PLATFORM
JOYSTICK – OUT
OF RANGE HIGH

2230

1

Hydraulic functions

(Lift and Telescope) associated to
the dual-axis platform joystick are

inhibited.

The platform module detects the

input voltage for dual-axis joystick is

out of range on the high side and

reports the issue to the UGM.

Power cycle.

PLATFORM
JOYSTICK –
CENTER TAP BAD

2231

1

Hydraulic functions

(Lift and Telescope) associated to
the dual-axis platform joystick are

inhibited.

The platform module detects center

tap dual-axis joystick voltage is out

of range and reports the issue to

the UGM.

Power cycle.

FUNCTION ENABLE
RELAY – INVALID
SIGNAL

2233

1

Deactivate and inhibit platform

module output J2-19 Function

Enable Relay.

Deactivate and inhibit UGM output

J2-26 Engage Starter.

Suppress the “FUNCTION

ENABLE INPUTS – INVALID

SIGNAL STATES” fault.

J7-2 of the platform module is HIGH

and J2-4 Function Enable Integrity

Signal does not change states from

HIGH to LOW during the power-up

test sequence.

Power cycle.

GROUND
CONTROLS

23XXX

OPERATING MODE
INTERLOCK –
SHIFTER NOT IN
NEUTRAL

239

1

J2-26 Engage Starter output will be

deactivated and engine start will

not be permitted if the PLATFORM

STATION is active and CABIN

MODE was the last valid operating

mode.

Changeover to PLATFORM MODE

will not be permitted.

The PLATFORM STATION is active

and CABIN MODE was the last

valid operating mode and a platform

is detected as attached and the

drive direction inputs are not

detected as follows: (J4-4 Neutral-
HIGH, J7-22 Forward-LOW, J4-18

LOW).

A valid drive

direction of

Neutral exists

(J4-4 is the

only HIGH

shifter input).

Message

Fault

Code

Indicators

Other Actions Taken

Trigger for Fault

Latch Until