Electrical System

9-58

3508PS, 3509PS, 3512PS, 3513PS, 4008PS, 4009PS, 4012PS, 4013PS, 4017PS, 40.8, 40.9

BOOM ANGLE
SENSOR – NOT
RESPONDING

2346

1

Display the fixed boom angle value

of ‘99’ on the operator’s cabin

display.

Temporarily assign a fixed boom

angle value of 99×.

Disallow boom angle sensor
calibration (“BOOM ANGLE:

CALIBRATION FAIL”).

Ignore all hydraulic function

requests from the platform module.

Deactivate and inhibit the Lift Up

output if the platform is detected as

attached or PLATFORM MODE is

the current active mode; otherwise,

derate the MAX LIFT UP in the

PERSONALITIES menu screen by

the LIFT UP DERATE value in the

Constant Data tables.

J2-11 Main Lift Up Valve or J2-22

Main Lift Down Valve are active

operating at a current of at least 900

mA for a period of 4 seconds with

an ENGINE RUNNING condition

and no appreciable change set at

0.5 degrees (adjustable in

Constant Data) in the value at this

input. (Note, this fault will not be

report during boom angle sensor

calibration.)

Power cycled.

Message

Fault

Code

Indicators

Other Actions Taken

Trigger for Fault

Latch Until