Electrical System

9-88

3508PS, 3509PS, 3512PS, 3513PS, 4008PS, 4009PS, 4012PS, 4013PS, 4017PS, 40.8, 40.9

LSS CELL #3
ERROR

823

1, 14

Deactivate and inhibit the Lift Up

output.

Deactivate and inhibit the Lift Down

output.

Deactivate and inhibit the

Telescope Out output.

Deactivate and inhibit the

Telescope In output.

Deactivate and inhibit the Platform

Rotate Left output.

Deactivate and inhibit the Platform

Rotate Right output.

Deactivate and inhibit the Platform

Level Up output.

Deactivate and inhibit the Platform

Level Down output.

Deactivate platform module output

J2-19 Function Enable Relay.

Display the platform overloaded

screen on the cabin’s LCD.

The UGM has detected the

PLATFORM STATION is active and

the PLATFORM OPTION is

ENABLED and a platform is

detected as attached and the LSS

module is reporting a error with

regard to load cell #3.

Power cycled.

LSS CELL #4
ERROR

824

1, 14

Deactivate and inhibit the Lift Up

output.

Deactivate and inhibit the Lift Down

output.

Deactivate and inhibit the

Telescope Out output.

Deactivate and inhibit the

Telescope In output.

Deactivate and inhibit the Platform

Rotate Left output.

Deactivate and inhibit the Platform

Rotate Right output.

Deactivate and inhibit the Platform

Level Up output.

Deactivate and inhibit the Platform

Level Down output.

Deactivate platform module output

J2-19 Function Enable Relay.

Display the platform overloaded

screen on the cabin’s LCD.

The UGM has detected the

PLATFORM STATION is active and

the PLATFORM OPTION is

ENABLED and a platform is

detected as attached and the LSS

module is reporting a error with

regard to load cell #4.

Power cycled.

Message

Fault

Code

Indicators

Other Actions Taken

Trigger for Fault

Latch Until