4 technical data, 1 general data, 2 operating conditions – Lenze E82ZAFPC010 User Manual

Page 15: Technical data, General data, Operating conditions, 4technical data

Advertising
background image

Technical data

General data

4

l

15

EDS82ZAFPC010 EN 4.0

4

Technical data

4.1

General data

Field

Values

Order designation

E82ZAFPC001 (coated)
E82ZAFPC010 (PT design)

PUO ID number

0x00DA

Communication profile
(DIN 19245 Part 1 and Part 3)

l

PROFIBUS−DP−V0

Communication medium

RS485

Drive profile

l

DRIVECOM profile "Drive technology 20" (can be switched off)

Network topology

l

Without repeaters: line

l

With repeaters: line or tree

PROFIBUS stations

Slave

Baud rate [kbps]

9.6 ... 12000 (automatic detection)

Process data words

1 ... 10 words
(16 bits/word)

DP user data length

1 ... 10 process data words +
4 parameter data words

Max. number of bus devices

l

Standard: 32 (= 1 bus segment)

l

With repeaters: 125

Max. cable length per bus
segment

1200 m (depending on the baud rate and cable type used)

External DC−voltage supply

+24 V DC ±10 %, max. 80 mA

4.2

Operating conditions

Ambient conditions

Climate

Storage

IEC/EN 60721−3−1

1K3 (−25 to +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 to +70 °C)

Operation

Corresponding to the data of the Lenze standard device used (see documentation
of the standard device).

Pollution

EN 61800−5−1

Degree of pollution 2

Degree of protection

IP20 (protection against accidental contact according to NEMA 250 type 1)

Advertising