Codes

Monitoring codes

10

l

76

EDS82ZAFPC010 EN 4.0

C1513: Monitoring response time of PZD communication

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1513

23062

d

=

5A16

h

3000

0

[1 ms]

65535 FIX32

The value of the response monitoring time is provided by the master.

)

Note!

A change in the monitoring time becomes effective immediately.
Monitoring starts with the receipt of the first telegram.

The setting C1513 = 0 deactivates the monitoring function.

C1514: Monitoring reaction in case of PZD communication fault

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1514

23061

d

=

5A15

h

0

0

[1]

3 FIX32

0: no action

1: TRIP (fault)

2: controller inhibit (CINH)

3: quick stop (QSP)

If the master does not send a message within the response monitoring time (configurable
in C1513), the action set in this code is executed.

)

Note!

A change in the monitoring reaction becomes effective immediately.