8 parameter data transfer, Parameter data transfer – Lenze E82ZAFPC010 User Manual

Page 56

Advertising
background image

Parameter data transfer

8

l

56

EDS82ZAFPC010 EN 4.0

8

Parameter data transfer

PROFIBUS transmits parameter data and process data between the host (master) and the
drives connected to the bus (slaves). Depending on their time−critical nature, the data are
transmitted via different communication channels.

ƒ

Parameter data are transmitted via the parameter data channel.
– DRIVECOM parameter data channel
– PROFIdrive parameter data channel (DP−V0 / DP−V1)

ƒ

The parameter data channel provides access to all Lenze codes.

ƒ

In general, the transfer of parameter data is not time−critical.

ƒ

Parameter data are, for instance, operating parameters, diagnostic information and
motor data.

)

Note!

Cyclic writing to codes via PROFIBUS is only permissible if the automatic
parameter set storage of the controller C0003 is deactivated (value 0).

Advertising