Parameter data transfer – Lenze E82ZAFPC010 User Manual

Page 59

Advertising
background image

Parameter data transfer

DRIVECOM parameter data channel

Telegram structure

8

l

59

EDS82ZAFPC010 EN 4.0

Byte 2: Subindex

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

High byte

Index

Low byte

Data 4 /

Error 4

Data 3 /

Error 3

Data 2 /

Error 2

Data 1 /

Error 1

Additional addressing via the subindex is required for those codes that have a subcode (see
code table).

Example:

Code C0039 / subcode 3 addresses "NSET JOG" (50 % = Lenze setting)

Byte 3 / 4: index

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Service

Subindex

Index

High byte

Index

Low byte

Data 4 /

Error 4

Data 3 /

Error 3

Data 2 /

Error 2

Data 1 /

Error 1

The parameter or the Lenze code is selected with these two bytes according to the formula:

Index = 24575 − Lenze code number

Example:

The parameter C0012 (acceleration time) is to be addressed:

ƒ

24575 − 12 = 24563 = 5FF3

hex

ƒ

Entry in byte 3 (high byte): 5F

hex

ƒ

Entry in byte 4 (low byte): F3

hex

Advertising
This manual is related to the following products: