Commissioning

Commissioning steps

6

l

35

EDS82ZAFPC010 EN 4.0

Detailed
information

Description

Step

POW9: PWM voltage (MCTRL1−VOLT−ADD)

POW10: PWM angle (MCTRL1−PHI−ADD)

9.

Assign process data output words of the standard device to the process data
input words (PIW) of the master via C1510.

PROFIBUS
communication
manual

Lenze setting:

PIW1: DRIVECOM status word (DRIVECOM STAT)
PIW2: Output frequency with slip (MCTRL1−NOUT+SLIP)
PIW3: Output frequency without slip (MCTRL1−NOUT)
PIW4: Apparent motor current (MCTRL1−IMOT)
PIW5: Actual process controller value (PCTRL1−ACT)
PIW6: Process controller setpoint (PCTRL1−SET1)
PIW7: Process controller output (PCTRL1−OUT)
PIW8: Controller load (MCTRL1−MOUT)
PIW9: DC−bus voltage (MCTRL1−DCVOLT)

PIW10: Ramp function generator input (NSET1−RFG1−IN)

10.

Enable process output data via C1512 = 65535.

l

Only required if C1511 has been changed.

l

Deactivate process data words that are not used by setting the respective
subcode of code C1511 to 0.

l

The value in C1512 is volatile, and all process data are enabled after every
switch−on.

11.

Enable standard device via terminal 28 (CINH).

l

Set terminal 28 to HIGH level.

12.

Enter the setpoint.

l

The master transmits the setpoint via the process data output word
selected.

13.

Change to the READY TO START status:

l

The master transmits the DRIVECOM control word:
0000 0000 0111 1110

bin

(007E

hex

).

PROFIBUS
communication
manual

14.

The standard device is in the READY TO START status.

l

The master receives the DRIVECOM status word:
xxxx xxxx x01x 0001

bin

15.

Change to the OPERATION ENABLED status.

l

The master transmits DRIVECOM control word:
0000 0000 0111 1111

bin

(007F

hex

).

16.

Now the drive starts up.