4 terminal assignment, Terminal assignment, Installation – Lenze E82ZAFPC010 User Manual

Page 28: Electrical installation terminal assignment

Advertising
background image

Installation

Electrical installation
Terminal assignment

5

l

28

EDS82ZAFPC010 EN 4.0

5.2.4

Terminal assignment

E82ZAFPC001function module

GND1

GND1

B CN

7

20 59

+5V

+20V

A

VP

28

39

7

B

A

GND2

40

GND3

+

X3

E82ZAFP001

Terminal
X3/

Designation

Function / level

+

PES

Additional HF−shield termination

A

T/R(A)

RS485 data line A

B

T/R(B)

RS485 data line B

CN

CNTR

For function see PROFIBUS standard *)

l

Level during data transmission: CNTR = HIGH
(+5 V DC, reference: GND3)

VP

For function see PROFIBUS standard *)

l

U = +5 V DC (reference: GND3)

l

I

max

= 10 mA

40

GND3

Reference potential for PROFIBUS network *)

7

GND1

Reference potential for X3/20

39

GND2

Reference potential for controller inhibit (CINH) at X3/28

28

CINH

Controller inhibit

l

Start = HIGH (+12 ... +30 V DC)

l

Stop = LOW (0 ... +3 V DC)
(reference: GND2)

20

DC voltage source for internal supply of controller inhibit (CINH)

l

+20 V DC (reference: GND1)

l

I

max

= 20 mA

59

External DC voltage supply for the function module

l

+24 V DC

± 10% (reference: GND1)

l

Current consumption on 24 V DC: 80 mA

The current for looping through the supply voltage to other nodes via
terminal 59 must be max. 3 A.

*) E.g. for repeater connection