Codes, Diagnostics codes, C1526: display of last configuration data – Lenze E82ZAFPC010 User Manual

Page 81: The type of the set parameter data channel, The length of the process data, Observe the descriptions concerning, The user data length ( ¶ 39), The meaning of consistency ( ¶ 87)

Advertising
background image

Codes

Diagnostics codes

10

l

81

EDS82ZAFPC010 EN 4.0

C1526: Display of last configuration data

Code

Subcode

Index

Possible settings

Data type

Lenze

Selection

C1526

23049

d

=

5A09

h

g

0

[1]

65535 FIX32

1: byte 1

2: byte 2

3: byte 3

This code displays the current configuration frame selected in the PROFIBUS master via the
GSE file.

The configuration data indicate the following (see table below):

ƒ

The type of the set parameter data channel

ƒ

The length of the process data

ƒ

The existence/non−existence of process data consistency

Consistent
channel

+ PZD ...

Subcode

Values

Description

DRIVECOM−PAR(Cons)

PZD(1W)

1

F3

hex

With consistent DRIVECOM parameter data channel and process data

2

70

hex ...

79

hex

With consistent DRIVECOM parameter data channel and process data
Process data without consistency
70

hex:

1 word ... 79

hex

: 10 words

PZD(1W Cons)

1

F3

hex

With consistent DRIVECOM parameter data channel and consistent
process data

2

F0

hex ...

F9

hex

With consistent DRIVECOM parameter data channel and consistent
process data
Process data with consistency
F0

hex:

1 word ... F9

hex

: 10 words

PKW(Cons)

PZD(1W)

1

00

hex

With consistent PROFIdrive parameter data channel and process data

2

F3

hex

With consistent PROFIdrive parameter data channel and process data,
in this case byte 1 is 00

hex

3

70

hex ...

79

hex

With consistent PROFIdrive parameter data channel and process data
Process data without consistency
70

hex:

1 word ... 79

hex

: 10 words

PZD(1W Cons)

1

00

hex

With consistent PROFIdrive parameter data channel and consistent
process data

2

F3

hex

With consistent PROFIdrive parameter data channel and consistent
process data, in this case byte 1 is 00

hex

3

F0

hex ...

F9

hex

With consistent PROFIdrive parameter data channel and consistent
process data
Process data with consistency
F0

hex:

1 word ... F9

hex

: 10 words

PZD(1W)

1

70

hex ...

79

hex

Process data without consistency
70

hex:

1 word ... 79

hex

: 10 words

PZD(1W Cons)

F0

hex ...

F9

hex

Process data with consistency
F0

hex:

1 word ... F9

hex

: 10 words

I

Tip!

Observe the descriptions concerning

ƒ

the user data length (

39)

ƒ

the meaning of consistency (

87)

Advertising
This manual is related to the following products: