Commissioning

Configuring the host system (master)

6

l

37

EDS82ZAFPC010 EN 4.0

Device data base file

The following configurations are saved in the device data base file LENZ00DA.GSE:

Modules in LENZ00DA.GSE

Parameter data

without/with consistency

Process data

without/with consistency

Assigned

I/O memory

Without

With

Without

With

PAR (Cons.)

+ PZD (n Words)

·

n words

4 + n words

PAR (Cons.)

+ PZD (n Words Cons.)

·

n words

4 + n words

PAR

+ PZD (n Words)

·

n words

4 + n words

PZD (n Words)

Without parameter data channel

n words

n words

PZD (n Words Cons.)

Without parameter data channel

n words

n words

n = 1 ... 10

)

Note!

Device control via FIF status/control word
Device control is only possible if the DRIVECOM status machine (Lenze setting)
is switched off.

ƒ

Set C1510 /1 (PIW1) to the value 1":
FIF status word 1 (FIF−STAT1).

ƒ

Set C1511 /1 (POW1) to the value 1":
FIF control word 1 (FIF−CTRL1).

ƒ

Set C1512 to 65535" to reenable process output words.

For Lenze codes see (

69)

I

Tip!

Use overall consistency

ƒ

We recommend to use exclusively configurations with consistency for the
parameter data channel to avoid data conflicts between PROFIBUS−DP
master and host CPU.

ƒ

Please note that the processing of consistent data varies between hosts.
This must be considered in the PROFIBUS−DP application program.

ƒ

Detailed description of consistency: (

87)