Electrical installation
Wiring with a host (master)

5

l

24

EDS82ZAFPC010 EN 4.0

Specification of the transmission cable

)

Note!

Only use cables complying with the listed specifications of the PROFIBUS user
organisation.

Field

Values

Specific resistance

135 ... 165

W/km, (f = 3 ... 20 MHz)

Capacitance per unit length

£ 30 nF/km

Loop resistance

< 110

W/km

Core diameter

> 0.64 mm

Core cross−section

> 0.34 mm

2

Cores

Twisted double, insulated and shielded

Bus cable length

The length of the bus cable depends on the baud rate used:

Baud rate [kbps]

Length [m]

9.6 ... 93.75

1200

187.5

1000

500

400

1500

200

3000 ... 12000

100

)

Note!

The baud rate depending on the data volume, cycle time, and number of nodes
should only be selected as high as required for the application.

I

Tip!

For high baud rates we recommend to consider the use of optical fibres.
Advantages of optical fibres:

ƒ

On the transmission path external electromagnetic interference remains
ineffective.

ƒ

Bus lengths of several kilometres are also possible with higher baud rates.
The bus length
– is irrespective of the baud rate.
– depends on the optical fibre used.