Technical data

Protective insulation

4

l

16

EDS82ZAFPC010 EN 4.0

4.3

Protective insulation

{

Danger!

Dangerous electrical voltage
If Lenze controllers are used on a phase earthed mains with a rated mains
voltage

³ 400 V, protection against accidental contact is not ensured without

implementing external measures.
Possible consequences:

ƒ

Death or serious injury

Protective measures:

ƒ

If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
– a double isolating distance must exist.
– the components to be connected must be provided with the second

isolating distance.

E82ZAFPC001function module

Protective insulation between bus and ...

Type of insulation (according to EN 61800−5−1)

l

Power section

– 8200 vector

Reinforced insulation

– 8200 motec

Reinforced insulation

– starttec

Reinforced insulation

l

Reference earth / PE (X3/7)

Functional insulation

l

External supply (X3/59)

Functional insulation

l

Terminal X3/20

Functional insulation

l

Terminal X3/28

Functional insulation

E82ZAFPC010 function module

Insulation between bus and ...

Type of insulation (in accordance with EN 61800−5−1)

l

8200 vector power stage

Reinforced insulation

l

Reference earth / PE (X3.2/7, X3.3/7)

Functional insulation

l

External supply (X3.2/59)

Functional insulation

l

Supply for CINH (X3.3/20)

Functional insulation

l

Controller inhibit, CINH (X3.3/28)

Functional insulation