3 types 8225 to 8227, Technical data – Lenze 8240 HVAC Series User Manual

Page 14

Advertising
background image

Technical Data

3-4

UOOuhäáã~_^NMMO

3.2.3

Types 8225 to 8227

120 % overload

Type

8225

4)

8226

8227

4)

Order no.

EVF8225-E-

V020

EVF8226-E-

V020

EVF8227-E-

V020

Mains voltage

V

rated

[V]

320 V - 0% ≤V

rated

≤440 V + 0% ;

45 Hz

¼ 65 Hz 0%

Alternative DC supply

V

DC

[V]

460 V - 0% ≤ V

DC

≤ 620 V + 0%

Mains current
with mains filter/mains choke

I

mains

[A]

119

144

185

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

DC

≤ 620 V

Motor power (4 pole ASM)

ff

/

P

rated

[kW]

75

90

110

p

( p

)

off 4kHz/8kHz*

P

rated

[hp]

100

120

148

Output power U, V, W

off 4 kHz/8 kHz*

S

rated4

[kVA]

S

rated8

[kVA]

91.5
76.2

110

103.9

142

124.7

Output power +U

G

, -U

G

1)

P

DC

[kW]

0

28.1

40.8

Output

4 kHz*

I

rated4

[A]

135

159

205

p

current

8 kHz*

I

rated8

[A]

110

150

171

12 kHz*

I

rated12

[A]

88

120

126

16 kHz*

I

rated16

[A]

77

105

108

noise optimized 4 kHz*

I

rated4

[A]

110

150

159

5)

noise optimized 8 kHz*

I

rated8

[A]

76

5)

92

5)

100

5)

noise optimized 12 kHz*

I

rated12

[A]

66

82

90

noise optimized 16 kHz*

I

rated16

[A]

60

67

72

Max. output

f

4 kHz*

I

rated max4

[A]

165

225

270

p

current for

60s

2)

8 kHz*

I

rated max8

[A]

165

225

221

60s

2)

12 kHz*

I

rated max12

[A]

114

156

164

16 kHz*

I

rated max16

[A]

100

136

140

noise optimized 4 kHz*

I

rated max4

[A]

165

225

238

5)

noise optimized 8 kHz*

I

rated max8

[A]

114

5)

138

5)

150

5)

noise optimized 12 kHz*

I

rated max12

[A]

85

107

117

noise optimized 16 kHz*

I

rated max16

[A]

78

87

94

Motor voltage

3)

V

M

[V]

0 - 3 ×V

mains

/ 0Hz

¼ 50Hz, if required up to 480Hz

Power loss (Operation with I

Nx

)

P

v

[W]

1470

2100

2400

Power derating

[%/K]

[%/m]

40

°C < T

amb

< 50

°C: 2.5%/K

1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5%/1000m

Field

f

Resolution

absolute

0.02 Hz

frequency

Digital setpoint selection

Accuracy

0.05 Hz

Analog setpoint selection

Linearity

0.5 % (max. selected signal level: 5 V or 10 V)

g

p

Temperature sensitivity

0

¼ 40 °C: +0.4 %

Offset

0 %

Weight

m [kg]

36.5

59

59

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I

Nx

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

4)

Max. permissible ambient temperature during operation +35

°C

5)

must only be operated with C144 = -1- (automatic chopper frequency reduction at

J

max

= -5

°C). Ensure not to

exceed the currents.

*

Chopper frequency of the inverter

Show/Hide Bookmarks