2 short set-up (factory setting), 1 switch-on sequence, Commissioning – Lenze 8240 HVAC Series User Manual

Page 42

Advertising
background image

Commissioning

5-2

UOOuhäáã~_^NMMO

5.2

Short set-up (factory setting)

5.2.1

Switch-on sequence

Step
1.Switch on mains voltage
2.Select the direction of rotation.

D

CW rotation:
- Apply a LOW signal to terminal E4 (0...+3V).

D

CCW rotation:
- Apply a HIGH signal to terminal E4 (+12...+30V).

3.Select the setpoint.

Apply a voltage 0...+10 V to terminal 8.

4.Enable the controller.

Apply a HIGH signal (+12...+30V) to terminal 28.

5.The drive is now operating according to factory setting.

5.2.2

Factory setting of the most important drive parameters

Setting

Code

Factory setting

Adaption to

the application

Operating mode

C001

-0-

Setpoint selection via terminal 8
Control via terminals
Parameter setting via 8201BB

See code table,

chapter 7.2

Terminal configuration

C007

-0-

E4

E3

E2 E1

CW/CCWDC brakeJOG1/2/3

See code table,

chapter 7.2

Machine data

Chapter 5.3 ff.

Speed range

Min. field frequency

C010 0.00 Hz

Chapter 5.3.1

p

g

Max. Field frequency

C011 50.00 Hz

p

Acceleration and

deceleration

Acceleration time

C012

5.00 s

Chapter 5.3.2

deceleration

times

Deceleration time

C013

5.00 s

Current limit

l

Motor mode

C022

150 %

Chapter 5.3.3

values

Generator mode

C023

80 %

p

Drive performance

Chapter 5.4 ff.

Current,
torque,

Operating mode

C014

-4-

Motor-current control

Motor-current

control

torque,
power

characteristic

V/f rated frequency

C015 50.00 Hz

control

chapter 5.4.2.2
V/f characteristic

control

V

min

setting

C016

0,00 %

control

D

with constant

V

min

boost, see

Slip compensation

C021

0,0 %

V

min

boost, see

chapter

5.4.2.1

Show/Hide Bookmarks

Advertising