2 types 8225 to 8227, Technical data – Lenze 8240 HVAC Series User Manual
Page 18
![background image](/manuals/566193/18/background.png)
Technical Data
3-8
UOOuhäáã~_^NMMO
3.3.2
Types 8225 to 8227
150 % overload
Type
8225
8226
8227
Mains voltage
V
rated
[V]
320 V - 0% ≤V
rated
≤528 V + 0% ; 45 Hz ¼ 65 Hz 0%
Alternative DC supply
V
DC
[V]
460 V - 0% ≤ V
DC
≤740 V + 0%
Mains current
with mains filter/mains choke
without mains filter/mains choke
I
mains
[A]
I
mains
[A]
100
--
135
--
165
--
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V
DC
≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ;
460 V ≤ V
DC
≤ 740 V
400 V
480 V
400 V
480 V
400 V
480 V
Motor power (4 pole ASM)
4 kH /8 kH *
P
rated
[kW]
55
75
75
90
90
110
p
( p
)
at 4 kHz/8 kHz*
P
rated
[hp]
74
100
100
120
120
148
Output power U, V, W
at 4kHz/8 kHz*
S
rated8
[kVA]
76.2
91.4
103.9
124
124.7
149
Output power +U
G
, -U
G
1)
P
DC
[kW]
0
0
28.1
32.4
40.8
47.1
Output
4 kHz*
I
rated4
[A]
110
105
150
142
180
171
p
current
8 kHz*
I
rated8
[A]
110
105
150
142
171
162
12 kHz*
I
rated12
[A]
88
83
120
112
126
117
16 kHz*
I
rated16
[A]
77
72
105
98
108
99
noise optimized 4 kHz*
I
rated4
[A]
110
104
150
141
159
3)
149
3)
noise optimized 8 kHz*
I
rated8
[A]
76
3)
71
3)
92
3)
86
3)
100
3)
94
3)
noise optimized 12 kHz*
I
rated12
[A]
66
60
82
75
90
81
noise optimized 16 kHz*
I
rated16
[A]
60
55
67
60
72
63
Max.
4 kHz*
I
rated max4
[A]
165
157
225
213
270
256
output
current
8 kHz*
I
rated max8
[A]
165
157
225
213
221
211
current
for für
12 kHz*
I
rated max12
[A]
114
108
156
147
164
153
for für
60s
2)
16 kHz*
I
rated max16
[A]
100
94
136
128
140
130
60s
)
noise optimized 4 kHz*
I
rated max4
[A]
165
156
225
212
238
3)
223
3)
noise optimized 8 kHz*
I
rated max8
[A]
114
3)
107
3)
138
3)
169
3)
150
3)
1413)
noise optimized 12 kHz*
I
rated max12
[A]
85
78
107
98
117
106
noise optimized 16 kHz*
I
rated max16
[A]
78
72
87
78
94
83
Power loss (Operation with I
Nx
)
P
v
[W]
1470
1960
2400
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I
Nx
.
3)
must only be operated with C144 = -1- (automatic chopper frequency reduction at
J
max
= +5
°C). Ensure not to
exceed the currents.
*
Chopper frequency of the inverter
For all other data see chapter 3.2.3.