2 types 8225 to 8227, Technical data – Lenze 8240 HVAC Series User Manual

Page 18

Advertising
background image

Technical Data

3-8

UOOuhäáã~_^NMMO

3.3.2

Types 8225 to 8227

150 % overload

Type

8225

8226

8227

Mains voltage

V

rated

[V]

320 V - 0% ≤V

rated

≤528 V + 0% ; 45 Hz ¼ 65 Hz 0%

Alternative DC supply

V

DC

[V]

460 V - 0% ≤ V

DC

≤740 V + 0%

Mains current
with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

I

mains

[A]

100

--

135

--

165

--

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

DC

≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ;

460 V ≤ V

DC

≤ 740 V

400 V

480 V

400 V

480 V

400 V

480 V

Motor power (4 pole ASM)

4 kH /8 kH *

P

rated

[kW]

55

75

75

90

90

110

p

( p

)

at 4 kHz/8 kHz*

P

rated

[hp]

74

100

100

120

120

148

Output power U, V, W

at 4kHz/8 kHz*

S

rated8

[kVA]

76.2

91.4

103.9

124

124.7

149

Output power +U

G

, -U

G

1)

P

DC

[kW]

0

0

28.1

32.4

40.8

47.1

Output

4 kHz*

I

rated4

[A]

110

105

150

142

180

171

p

current

8 kHz*

I

rated8

[A]

110

105

150

142

171

162

12 kHz*

I

rated12

[A]

88

83

120

112

126

117

16 kHz*

I

rated16

[A]

77

72

105

98

108

99

noise optimized 4 kHz*

I

rated4

[A]

110

104

150

141

159

3)

149

3)

noise optimized 8 kHz*

I

rated8

[A]

76

3)

71

3)

92

3)

86

3)

100

3)

94

3)

noise optimized 12 kHz*

I

rated12

[A]

66

60

82

75

90

81

noise optimized 16 kHz*

I

rated16

[A]

60

55

67

60

72

63

Max.

4 kHz*

I

rated max4

[A]

165

157

225

213

270

256

output

current

8 kHz*

I

rated max8

[A]

165

157

225

213

221

211

current

for für

12 kHz*

I

rated max12

[A]

114

108

156

147

164

153

for für

60s

2)

16 kHz*

I

rated max16

[A]

100

94

136

128

140

130

60s

)

noise optimized 4 kHz*

I

rated max4

[A]

165

156

225

212

238

3)

223

3)

noise optimized 8 kHz*

I

rated max8

[A]

114

3)

107

3)

138

3)

169

3)

150

3)

1413)

noise optimized 12 kHz*

I

rated max12

[A]

85

78

107

98

117

106

noise optimized 16 kHz*

I

rated max16

[A]

78

72

87

78

94

83

Power loss (Operation with I

Nx

)

P

v

[W]

1470

1960

2400

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I

Nx

.

3)

must only be operated with C144 = -1- (automatic chopper frequency reduction at

J

max

= +5

°C). Ensure not to

exceed the currents.

*

Chopper frequency of the inverter
For all other data see chapter 3.2.3.

Show/Hide Bookmarks

Advertising