5 types 8244 to 8246, Technical data – Lenze 8240 HVAC Series User Manual

Page 16

Advertising
background image

Technical Data

3-6

UOOuhäáã~_^NMMO

3.2.5

Types 8244 to 8246

120 % overload

Type

8244

8245

8246

Order no.

EVF8244-E-

V020

EVF8245-E-

V020

EVF8246-E-

V020

Mains voltage

V

rated

[V]

320V 0% ≤ V

rated

≤ 440 V 0% ;

45Hz

¼ 65Hz 0%

Alternative DC supply

V

DC

[V]

460V 0% ≤ V

DC

≤ 620V 0%

Mains current
with mains filter/mains choke

I

mains

[A]

8.8

15.0

20.5

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

DC

≤ 620 V

Motor power (4 pole ASM)

ff

/

P

rated

[kW]

4.4

7.5

11.0

p

( p

)

off 4kHz/8kHz*

P

rated

[hp]

5.4

10.0

15.0

Output power U, V, W

off 4 kHz/8 kHz*

S

rated4

[kVA]

S

rated8

[kVA]

6.5
4.8

11.1

9.0

16.3
16.3

Output power +U

G

, -U

G

1)

P

DC

[kW]

2.0

0

0

Output

4 kHz*

I

rated4

[A]

9.2

16.0

23.5

p

current

8 kHz*

I

rated8

[A]

7.0

13.0

23.5

12 kHz*

I

rated12

[A]

6.3

11.7

20.0

16 kHz*

I

rated16

[A]

5.6

10.4

16.5

noise optimized 4 kHz*

I

rated4

[A]

7.0

13.0

23.5

noise optimized 8 kHz*

I

rated8

[A]

6.0

11.1

20.0

noise optimized 12 kHz*

I

rated12

[A]

6.1

11.3

19.4

noise optimized 16 kHz*

I

rated16

[A]

5.2

9.7

15.2

Max. output

f

4 kHz*

I

rated max4

[A]

11.0

19.5

35.3

p

current for

60s

2)

8 kHz*

I

rated max8

[A]

10.5

19.5

35.0

60s

2)

12 kHz*

I

rated max12

[A]

9.5

17.5

30.0

16 kHz*

I

rated max16

[A]

8.4

15.6

24.6

noise optimized 4 kHz*

I

rated max4

[A]

10.5

19.5

35.5

noise optimized 8 kHz*

I

rated max8

[A]

7.8

14.5

22.9

noise optimized 12 kHz*

I

rated max12

[A]

9.1

16.5

29.0

noise optimized 16 kHz*

I

rated max16

[A]

7.8

14.5

22.9

Motor voltage

3)

V

M

[V]

0 - 3 ×V

mains

/ 0Hz

¼ 50Hz, if required up to 480Hz

Power loss (Operation with I

Nx

)

P

v

[W]

165

260

360

Power derating

[%/K]

[%/m]

40

°C < T

amb

< 50

°C: 2.5%/K

1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5%/1000m

Field

f

Resolution

absolute

0.02 Hz

frequency

Digital setpoint selection

Accuracy

0.05 Hz

Analog setpoint selection

Linearity

0.5 % (max. selected signal level: 5 V or 10 V)

g

p

Temperature sensitivity

0

¼ 40 °C: +0.4 %

Offset

0 %

Weight

m [kg]

5.0

7.5

7.5

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I

Nx

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

*

Chopper frequency of the inverter

Show/Hide Bookmarks

Advertising