4 types 8244 to 8246, Technical data – Lenze 8240 HVAC Series User Manual

Page 20

Advertising
background image

Technical Data

3-10

UOOuhäáã~_^NMMO

3.3.4

Types 8244 to 8246

150 % overload

Type

8244

8245

8246

Mains voltage

V

rated

[V]

320 V - 0% ≤ Vrated ≤ 528 V + 0% ; 45 Hz 065 Hz ”0%

Alternative DC supply

V

DC

[V]

460 V - 0% ≤ V

DC

≤ 740 V + 0%

Mains current
with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

I

mains

[A]

7.0

-

12.0
16.8

20.5

-

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

DC

≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ;

460 V ≤ V

DC

≤ 740 V

400 V

480 V

400 V

480 V

400 V

480 V

Motor power (4 pole ASM)

4 kH /8 kH *

P

rated

[kW]

3.0

3.0

5.5

5.5

11.0

11.0

p

( p

)

at 4 kHz/8 kHz*

P

rated

[hp]

4.0

4.0

7.5

7.5

15.0

15.0

Output power U, V, W

at 4kHz/8 kHz*

S

rated8

[kVA]

4.8

5.8

9.0

10.8

16.3

10.8

Output power +U

G

, -U

G

1)

P

DC

[kW]

2.0

2.5

0

0

0

0

Output

4 kHz*

I

rated4

[A]

7.0

7.0

13.0

13.0

23.5

23.5

p

current

8 kHz*

I

rated8

[A]

7.0

7.0

13.0

13.0

23.5

23.5

12 kHz*

I

rated12

[A]

6.3

6.3

11.7

11.7

20.0

19.1

16 kHz*

I

rated16

[A]

5.6

5.6

10.4

10.4

16.5

15.7

noise optimized 4 kHz*

I

rated4

[A]

7.0

6.6

13.0

12.3

23.5

22.1

noise optimized 8 kHz*

I

rated8

[A]

6.0

5.6

11.1

10.4

20.0

18.8

noise optimized 12 kHz*

I

rated12

[A]

6.1

6.1

11.3

11.3

19.4

18.4

noise optimized 16 kHz*

I

rated16

[A]

5.2

5.2

9.7

9.7

15.2

14.6

Max.

4 kHz*

I

rated max8

[A]

10.5

10.5

19.5

19.5

35.0

33.5

output

current

8 kHz*

I

rated max8

[A]

10.5

10.5

19.5

19.5

35.0

33.5

current

for für

12 kHz*

I

rated max12

[A]

9.5

9.5

17.5

17.5

30.0

28.7

for für

60s

2)

16 kHz*

I

rated max16

[A]

8.4

8.4

15.6

15.6

24.6

23.6

60s

)

noise optimized 4 kHz*

I

rated max4

[A]

10.5

8.4

19.5

15.6

35.5

28.2

noise optimized 8 kHz*

I

rated max8

[A]

7.8

7.8

14.5

14.5

22.9

21.8

noise optimized 12 kHz*

I

rated max12

[A]

9.1

9.1

16.5

16.5

29.0

27.6

noise optimized 16 kHz*

I

rated max16

[A]

7.8

7.8

14.5

14.5

22.9

21.8

Power loss (Operation with I

Nx

)

P

v

[W]

150

210

360

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I

Nx

.

*

Chopper frequency of the inverter
For all other data see chapter 3.2.5.