Configuration – Lenze 8240 HVAC Series User Manual

Page 69

Advertising
background image

Configuration

7-5

UOOuhäáã~_^NMMO

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Selection

Lenze

Name

C008

¿ Function relay K1

-1-

-0-

Ready for operation

-1-

TRIP fault message

-2-

Motor is running

-3-

Motor is running / CW rotation

-4-

Motor is running / CCW rotation

-5-

Field frequency f

d

= 0

-6-

f

dset

reached

-7-

Q

min

reached

-8-

I

max

reached

-9-

Overtemperature (

J

max

-10

°C)

-10-

TRIP or Q

min

or IMP

822X/824X

-11-

PTC warning

-12-

Apparent motor current (C054) < threshold

C156

-13-

Apparent motor current (C054) < threshold

C156 and f

d

> Q

min

threshold (C017)

-14-

Apparent motor current (C054) < threshold

C156 and input of ramp function generator

= output of ramp function generator

822X/824X

-15-

Warning motor phase failure

-16-

f

d

(C050) < f

dmin

(C010)

C009* Device address

1

1

{1}

99

Only for LECOM

applications

C010 Minimum field

frequency

0.00

0.00

{0.02Hz}

480.00

C011 Maximum field

frequency

50.00 7.50

{0.02Hz}

480.00

C012 Acceleration time

5.00

0.00

{0.02s}

1300.00

C013 Deceleration time

5.00

0.00

{0.02s}

1300.00

C014

¿ Operating mode

-2-

Linear characteristic V~f

d

with constant

V

min

boost

V

min

boost

-3-

Square characteristic V~f

d

2

with constant

V

min

boost

-4-

-4-

Motor-current control

C015 V/f rated frequency 50.00 7.50

{0.02Hz}

960.00

C016 V

min

setting

0.00

0.00

{0.2 %}

40.0

depends on the unit

C017 Threshold Q

min

0.00

0.00

{0.02Hz}

480.00

C018

¿ Chopper frequency

-1-

-0-

4kHz reduced power loss

-1-

8kHz,reduced power loss

-2-

12kHz reduced power loss

-3-

16kHz reduced power loss

3

16kHz reduced power loss

-4-

4kHz reduced noise emission

-5-

8kHz reduced noise emission

-6-

12 kHz reduced noise emission

-7-

16 kHz reduced noise emission

C019 Threshold auto DC

brake

0.10

0.00

{0.02Hz}

5.00

C021 Slip

0 0

-50 0

{0 1 %}

50 0

* when C014 = 2 3

C021 Slip

ti

0,0

-50.0

{0.1 %}

50.0

* when C014 = 2, 3

p

compensation

0.0

0.0

{0.1 %}

20.0

* when C014 = 4

* depends on the unit

C022 I

max

limit

motor mode

150

30

{1 %}

150