3 single drives with 150 % overload, Technical data – Lenze 8240 HVAC Series User Manual
Page 22
![background image](/manuals/566193/22/background.png)
Technical Data
3-12
UOOuhäáã~_^NMMO
3.4.3
Single drives with 150 % overload
qЬЙ н~ДдЙ о~дмЙл ~кЙ о~дбЗ Сзк нЬЙ зйЙк~нбзе зС UOuu ЕзенкзддЙкл ~л лбеЦдЙ ЗкбоЙл пбнЬ
~ г~нЕЬбеЦ гзнзк ~еЗ NRM B зоЙкдз~ЗK
Type
Mains input L1, L2, L3, PE/motor connection U, V, W, PE
yp
Operation without mains filter/mains choke
Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b.
Cable cross-section
1)
Fuse
F1, F2, F3
E.l.c.b.
Cable cross-section
1)
VDE
UL
VDE
mm
2
AWG
VDE
UL
VDE
mm
2
AWG
8221 63A
--
--
16
5
M 35A
35A
--
10
7
8222 --
--
--
--
--
M 50A
50A
--
16
5
8223 --
--
--
--
--
M 80A
80A
--
25
3
8224 --
--
--
--
--
M 100A
100A
--
50
0
8225 --
--
--
--
--
M 125A
125A
--
70
2 / 0
8226 --
--
--
--
--
M 160A
175A
--
95
3 / 0
8227 --
--
--
--
--
M 200A
200A
--
120
4 / 0
8241 M 6A
5A
B 6A
1
17
M 6A
5A
B 6A
1
17
8242 M 6A
5A
B 6A
1
17
M 6A
5A
B 6A
1
17
8243 M 10A
10A
B 10A
1.5
15
M 10A
10A
B 10A
1.5
15
8244 --
--
--
--
--
M 10A
10A
B 10A
1.5
15
8245 M 25A
25A
B 25A
6
10
M 20A
20A
B 20A
4
11
8246 --
--
--
--
--
M 32A
25A
B 32A
6
10
1)
Observe national and regional regulations (e. g. VDE/EVU)!
Show/Hide Bookmarks