3 maloperation of the drive, 2 fault analysis using the history buffer, Troubleshooting and fault elimination – Lenze 8240 HVAC Series User Manual

Page 78

Advertising
background image

Troubleshooting and fault elimination

8-2

UOOuhäáã~_^NMMO

8.1.3

Maloperation of the drive

Maloperation

Possible causes

Motor does not rotate

D

DC-bus voltage too low

(Red LED is blinking every 0.4 seconds; message LU is displayed)

D

Controller inhibited

(green LED is blinking, display of the operating module: OFF, STOP or AS_LC)

D

Setpoint = 0

D

DC braking active

D

Quick-stop function active

D

JOG setpoint activated and JOG frequency = 0

D

Fault message is displayed (see chapter 8.3 )

D

Mechanical motor brake is not released

Motor does not rotate

smoothly

D

Defective motor cable

D

Maximum current C022 and C023 too low

D

Motor underexcited or overexcited (check parameter setting)

Current consumption of

motor too high

D

Setting of C016 too high

D

Setting of C015 too low

D

C088 and C091 are not adapted to the motor data.

8.2

Fault analysis using the history buffer

qЬЙ Ьблнзку ДмССЙк бл млЙЗ нз нк~ЕЙ С~ìäíëK qЬЙ С~мдн гЙлл~ЦЙл ~кЙ лнзкЙЗ бе нЬЙ Ьблнзку

ДмССЙк бе нЬЙ зкЗЙк зС нЬЙбк çÅÅìêêÉåÅÉK
qЬЙ гЙгзку дзЕ~нбзел Е~е ДЙ кЙнкбЙоЙЗ об~ нЬЙ ÅçÇÉëK

Structure of the history buffer
Code

C0168

Entry

Note

C161

Memory location 1

Active fault

If the fault is no longer active or has been acknowledged:

D

The contents of the memory locations 1 3 will be saved in a

C162

Memory location 2

Last fault

D

The contents of the memory locations 1-3 will be saved in a

”higher” location.

C163

Memory location 3

Last but one fault

higher location.

D

The contents of the memory location 4 will be eliminated from

the history buffer and cannot be read any longer

C164

Memory location 4

Last but two fault

the history buffer and cannot be read any longer.

D

Memory location 1 will be deleted (= no active fault).

Show/Hide Bookmarks