Configuration – Lenze 8240 HVAC Series User Manual
Page 70
![background image](/manuals/566193/70/background.png)
Configuration
7-6
UOOuhäáã~_^NMMO
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C023 I
max
limit
generator mode
80
30
{1 %}
150
The current-limit
controller for
operation in
generator mode is
not active at 30 %.
C026* Offset adjustment
analog input
0.00
-10.00
{0.01 V}
10.00
C027* Scaling factor of
analog input
100.0 -200.0
{0.1 %}
200.0
C034
¿ Master current
-0-
-0-
0 to 20mA /
0 to 5V / 0 to 10V
-1-
4 to 20mA
C035*
¿ Selection DC brake
-0-
-0-
Selection of brake voltage under C036
-1-
Selection of brake current under C036
C036 Voltage for DC
brake
*
0
{0.02 %}
150
* depends on the unit
C037 JOG value 1
20.00 -480.00
{0.02Hz}
480.00
C038 JOG value 2
30.00 -480.00
{0.02Hz}
480.00
C039 JOG value 3
40.00 -480.00
{0.02Hz}
480.00
C040 Controller enable
*
-0-
Controller inhibited
-1-
Controller enabled
* see Operating
Instructions 2102
C043 TRIP reset
*
-0-
No current fault
-1-
Current fault
* see Operating
Instructions 2102
C046 Frequency setpoint
*
-480.00
{0.02 %}
480.00
* see Operating
Instructions 2102
C047* Torque setpoint
I
max
limit value
Only display
D
C005 = 4, 5
- Torque setpoint
D
C005 =
1, 2, 3, 6, 7
- I
max
limit
value (C022)
C049* Additional setpoint
Only display
D
Only when
C005 = 1, 2
C050* Output frequency
Only display
C051* Actual PID
controller value
Only display
C052* Motor voltage
Only display
C053* DC-bus voltage
Only display
C054* Motor current
Only display
C056* Unit load
Only display
C061* Heat sink
temperature
Only display
C070 Gain
PID controller
1.00
0.00
{0.01}
300.00
0.0 = P-component
inactive
C071 Integral action time
PID controller
100
10ms
9999s
9999s = I-componen
t inactive
C072 Differential
component
PID controller
0.0
0.0
{0.1}
5.0
0.0 = D-component
inactive
C074 Influence PID
controller
0.0
0.0
{0.1 %}
100.0