3 rated data (operation with 150 % overload), 1 types 8221 to 8224, Technical data – Lenze 8240 HVAC Series User Manual

Page 17: 3 rated data

Advertising
background image

Technical Data

3-7

UOOuhäáã~_^NMMO

3.3

Rated data

(Operation with 150 % overload)

léÉê~нбзе йЙкгбннЙЗ пбнЬ ~ г~бел оздн~ЦЙ зС

P^` L QMM s J QUMs LRM eòLSM eò

3.3.1

Types 8221 to 8224

150 % overload

Type

8221

8222

8223

8224

Mains voltage

V

rated

[V]

320 V - 0% ≤V

rated

≤528 V + 0% ; 45 Hz ¼ 65 Hz 0%

Alternative DC supply

V

DC

[V]

460 V - 0% ≤ V

DC

≤740 V + 0%

Mains current
with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

I

mains

[A]

29.0
43.5

42.0

--

55.0

--

80.0

--

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

DC

≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ;

460 V ≤ V

DC

≤ 740 V

400 V

480 V

400 V

480 V

400 V

480 V

400 V

480 V

Motor power (4 pole ASM)

ff 4kH /8kH *

P

rated

[kW]

15

18.5

22

30

30

37

45

55

p

( p

)

off 4kHz/8kHz*

P

rated

[hp]

20

25

30

40

40

49.5

60

74

Output power U, V, W

off 4 kHz/8 kHz*

S

rated8

[kVA]

22.2

26.6

32.6

39.1

41.6

49.9

61.7

73.9

Output power +U

G

, -U

G

1)

P

DC

[kW]

10.2

11.8

4.0

4.6

0

0

5.1

5.9

Output

4 kHz*

I

rated4

[A]

32

32

47

47

59

56

89

84

p

current

8 kHz*

I

rated8

[A]

32

32

47

47

59

56

89

84

12 kHz*

I

rated12

[A]

27

25

40

37

50

47

62

67

16 kHz*

I

rated16

[A]

24

22

35

33

44

41

54

58

noise optimized 4 kHz*

I

rated4

[A]

32

30,5

47

45

59

56

89

84

noise optimized 8 kHz*

I

rated8

[A]

29

27

43

41

47

3)

44

3)

59

3)

55

3)

noise optimized 12 kHz*

I

rated12

[A]

25

24

37

35

44

38

54

48

noise optimized 16 kHz*

I

rated16

[A]

21

19

30

28

35

30

46

39

Max.

4 kHz*

I

rated max4

[A]

48

48

70.5

70.5

89

84

134

126

output

current

8 kHz*

I

rated max8

[A]

48

48

70.5

70.5

89

84

134

126

current

for für

12 kHz*

I

rated max12

[A]

40

38

59

56

75

70

92

87

for für

60s

2)

16 kHz*

I

rated max16

[A]

36

33

53

49

66

61

81

75

60s

)

noise optimized 4 kHz*

I

rated max4

[A]

48

46

70.5

66,5

89

56

134

126

noise optimized 8 kHz*

I

rated max8

[A]

43

41

64

61

70

3)

65

3)

88

3)

82

3)

noise optimized 12 kHz*

I

rated max12

[A]

38

36

56

53

66

57

81

75

noise optimized 16 kHz*

I

rated max16

[A]

31

29

46

42

53

45

69

63

Power loss (Operation with I

Nx

)

P

v

[W]

430

640

810

1100

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I

Nx

.

3)

must only be operated with C144 = -1- (automatic chopper frequency reduction at

J

max

= +5

°C). Ensure not to

exceed the currents.

*

Chopper frequency of the inverter
For all other data see chapter 3.2.2.

Show/Hide Bookmarks

Advertising