Configuration – Lenze 8240 HVAC Series User Manual

Page 73

Advertising
background image

Configuration

7-9

UOOuhäáã~_^NMMO

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Selection

Lenze

Name

C115

¿ Priority mask

digital inputs

-0-

E4

E3

E2

E1

-0-

0

0

0

0

-1-

0

0

0

1

-2-

0

0

1

0

-3-

0

0

1

1

-4-

0

1

0

0

-5-

0

1

0

1

-6-

0

1

1

0

-7-

0

1

1

1

-8-

1

0

0

0

-9-

1

0

0

1

-10-

1

0

1

0

-11-

1

0

1

1

-12-

1

1

0

0

-13-

1

1

0

1

-14-

1

1

1

0

-15-

1

1

1

1

0: Function Ex

depends on C001
1: Function Ex is

independent of C001

D

Ctrl. inhibit and

TRIP reset always

have first priority.

D

With -0- also TRIP

set and QSP have

priority.

C117

¿ Function relay K2

-0-

-0-

Ready for operation

-1-

TRIP fault message

-2-

Motor is running

-3-

Motor is running / CW rotation

-4-

Motor is running / CCW rotation

-5-

Field frequency f

d

= 0

-6-

f

dset

reached

-7-

Q

min

reached

-8-

I

max

reached

-9-

Overtemperature (

J

max

-10

°C)

-10-

TRIP or Q

min

or IMP

822X/824X

-11-

PTC warning

-12-

Apparent motor current (C054) < threshold

C156

-13-

Apparent motor current (C054) < threshold

C156 and f

d

> Q

min

threshold (C017)

-14-

Apparent motor current (C054) < threshold

C156 and input of ramp function generator =

output of ramp function generator

822X/824X

-15-

Warning motor phase failure

-16-

f

d

(C050) < f

dmin

(C010)

C119

¿ Function PTC

822X/824X

-0-

-0-

PTC input not active

-1-

PTC input active, TRIP and pulse inhibit will

be set

-2-

PTC input active, warning

C120 I

2

¡

t switch off

822X/824X

0

0

{1 %}

100

C125

¿* LECOM baud rate

-0-

-0-

9600 baud

-1-

4800 baud

-2-

2400 baud

-3-

1200 baud

-4-

19200 baud

Only for LECOM

applications

Show/Hide Bookmarks