Configuration – Lenze 8240 HVAC Series User Manual
Page 73
Configuration
7-9
UOOuhäáã~_^NMMO
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C115
¿ Priority mask
digital inputs
-0-
E4
E3
E2
E1
-0-
0
0
0
0
-1-
0
0
0
1
-2-
0
0
1
0
-3-
0
0
1
1
-4-
0
1
0
0
-5-
0
1
0
1
-6-
0
1
1
0
-7-
0
1
1
1
-8-
1
0
0
0
-9-
1
0
0
1
-10-
1
0
1
0
-11-
1
0
1
1
-12-
1
1
0
0
-13-
1
1
0
1
-14-
1
1
1
0
-15-
1
1
1
1
0: Function Ex
depends on C001
1: Function Ex is
independent of C001
D
Ctrl. inhibit and
TRIP reset always
have first priority.
D
With -0- also TRIP
set and QSP have
priority.
C117
¿ Function relay K2
-0-
-0-
Ready for operation
-1-
TRIP fault message
-2-
Motor is running
-3-
Motor is running / CW rotation
-4-
Motor is running / CCW rotation
-5-
Field frequency f
d
= 0
-6-
f
dset
reached
-7-
Q
min
reached
-8-
I
max
reached
-9-
Overtemperature (
J
max
-10
°C)
-10-
TRIP or Q
min
or IMP
822X/824X
-11-
PTC warning
-12-
Apparent motor current (C054) < threshold
C156
-13-
Apparent motor current (C054) < threshold
C156 and f
d
> Q
min
threshold (C017)
-14-
Apparent motor current (C054) < threshold
C156 and input of ramp function generator =
output of ramp function generator
822X/824X
-15-
Warning motor phase failure
-16-
f
d
(C050) < f
dmin
(C010)
C119
¿ Function PTC
822X/824X
-0-
-0-
PTC input not active
-1-
PTC input active, TRIP and pulse inhibit will
be set
-2-
PTC input active, warning
C120 I
2
¡
t switch off
822X/824X
0
0
{1 %}
100
C125
¿* LECOM baud rate
-0-
-0-
9600 baud
-1-
4800 baud
-2-
2400 baud
-3-
1200 baud
-4-
19200 baud
Only for LECOM
applications