3 fault indications, Troubleshooting and fault elimination – Lenze 8240 HVAC Series User Manual

Page 79

Advertising
background image

Troubleshooting and fault elimination

8-3

UOOuhäáã~_^NMMO

8.3

Fault indications

Display

Fault

Cause

Remedy

---

No fault

-

-

EEr

External fault (TRIP-Set)

A digital input assigned to the TRIP-Set

function has been activated

Check external encoder

H05

Internal fault

Contact Lenze

LP1

Motor phase failure

D

Failure of one or several motor phases

D

Motor current too low

Check motor cables, check V

min

setting,

connect motor with corresponding power or

adapt motor under C599.

LU

Undervoltage

DC-bus voltage too low

D

Check mains voltage

D

Check supply module

OC1

Short circuit

Short circuit

Find out cause of short circuit; check cable

Excessive capacitive charging current of

the motor cable

Use motor cable which is shorter or of lower

capacitance

OC2

Earth fault

Grounded motor phase

Check motor; check cable

Excessive capacitive charging current of

the motor cable

Use motor cable which is shorter or of lower

capacitance

OC3

Overload inverter during

acceleration or short circuit

Acceleration time too short (C012)

D

Increase acceleration time

D

Check drive selection

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4

Overload controller during

deceleration

Deceleration time too short (C013)

D

Increase deceleration time

D

Check the selection of the brake resistor or

connect the brake chopper

OC5

I x t overload

Frequent and too long acceleration

processes with overcurrent

Check drive dimensioning

OC6

Overload motor

Motor is thermally overloaded, for

instance, because of

D

impermissible continuous current

D

Check drive selection

D

frequent or too long acceleration

processes

D

Check the setting under C120

OH

Heat sink temperature is

higher than the value set in

the controller

Ambient temperature

T

amb

> +40

°C or +50 °C

D

Allow controller to cool and ensure ventilation

D

Check the ambient temperature in the control

cabinet

Heat sink very dirty

Clean heat sink

Incorrect mounting position

Change mounting position

OH3

PTC monitoring (TRIP)

Motor too hot bec ause of exc essive

current or frequent and too long

acceleration

Check drive dimensioning

PTC not connected

Connect PTC or switch-off monitoring

(C0585=3)

OH4

Overtemperature unit

Inside unit too hot

D

Reduce controller load

D

Improve cooling

D

Check fan in the controller

OH51

PTC monitoring (Warning)

Motor too hot because of excessive

current or frequent and too long

acceleration

Check drive dimensioning

PTC not connected

Connect PTC or switch-off monitoring

(C0585=3)