3 types 8241 to 8243, Technical data – Lenze 8240 HVAC Series User Manual

Page 19

Advertising
background image

Technical Data

3-9

UOOuhäáã~_^NMMO

3.3.3

Types 8241 to 8243

150 % overload

Type

8241

8242

8243

Mains voltage

V

rated

[V]

320 V - 0% ≤ Vrated ≤ 528 V + 0% ; 45 Hz 065 Hz ”0%

Alternative DC supply

V

DC

[V]

460 V - 0% ≤ V

DC

≤ 740 V + 0%

Mains current
with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

I

mains

[A]

1.5
2.1

2.5
3.5

3.9
5.5

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

DC

≤ 620 V or 3 AC / 480 V / 50 Hz/60 Hz ;

460 V ≤ V

DC

≤ 740 V

400 V

480 V

400 V

480 V

400 V

480 V

Motor power (4 pole ASM)

4 kH /8 kH *

P

rated

[kW]

0.37

0.37

0.75

0.75

1.5

1.5

p

( p

)

at 4 kHz/8 kHz*

P

rated

[hp]

0.5

0.5

1.0

1.0

2.0

2.0

Output power U, V, W

at 4kHz/8 kHz*

S

rated8

[kVA]

1.0

1.2

1.7

2.1

2.7

3.2

Output power +U

G

, -U

G

1)

P

DC

[kW]

1.9

2.3

0.7

0.9

0

0

Output

4 kHz*

I

rated8

[A]

1.5

1.5

2.5

2.5

3.9

3.9

p

current

8 kHz*

I

rated8

[A]

1.5

1.5

2.5

2.5

3.9

3.9

12kHz*

I

rated12

[A]

1.35

1.35

2.2

2.2

3.5

3.5

16 kHz*

I

rated16

[A]

1.2

1.2

2.0

2.0

3.1

3.1

noise optimized 4 kHz*

I

rated4

[A]

1.5

1.5

2.5

2.4

3.9

3.7

noise optimized 8 kHz*

I

rated8

[A]

1.3

1.3

2.2

2.1

2.9

2.8

noise optimized 12 kHz*

I

rated12

[A]

1.3

1.3

2.1

2.1

3.4

3.4

noise optimized 16 kHz*

I

rated16

[A]

1.1

1.1

1.8

1.8

2.9

2.9

Max.

4 kHz*

I

rated max8

[A]

2.2

2.25

3.7

3.75

5.8

5.85

output

current

8 kHz*

I

rated max8

[A]

2.2

2.25

3.7

3.75

5.8

5.85

current

for für

12 kHz*

I

rated max12

[A]

2.0

2.0

3.3

3.3

5.2

5.2

for für

60s

2)

16 kHz*

I

rated max16

[A]

1.8

1.8

3.0

3.0

4.7

4.7

60s

)

noise optimized 4 kHz*

I

rated max4

[A]

2.3

2.2

3.8

3.6

5.8

5.5

noise optimized 8 kHz*

I

rated max8

[A]

2.0

1.8

3.2

3.0

5.0

4.7

noise optimized 12 kHz*

I

rated max12

[A]

1.9

1.9

3.2

3.2

5.1

5.1

noise optimized 16 kHz*

I

rated max16

[A]

1.6

1.6

2.7

2.7

4.3

4.3

Power loss (Operation with I

Nx

)

P

v

[W]

50

65

100

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I

Nx

.

*

Chopper frequency of the inverter
For all other data see chapter 3.2.4.