Configuration – Lenze 8240 HVAC Series User Manual
Page 72
Configuration
7-8
UOOuhäáã~_^NMMO
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C111
¿ Monitor signal
-0-
-0-
Field frequency
-1-
Unit load
-2-
Motor current
-3-
DC-bus voltage
-4-
Motor power
-5-
Motor voltage
-6-
Analog output 1/f
d
(1/C050)
-7-
Field frequency of
f
dmin
(C010) ... f
dmax
(C011)
-8-
Actual PID controller value
Selection -9- ... -25-
corresponds to the
relay output functions
C008 and C117:
D
LOW = 0 V
D
HIGH = 10 V
-9-
Ready for operation
-10-
TRIP fault message
-11-
Motor is running
-12-
Motor is running / CW rotation
-13-
Motor is running / CCW rotation
-14-
Field frequency f
d
= 0
-15-
f
dsoll
reached
-16-
Q
min
reached
-17-
I
max
reached
-18-
Overtemperature (Â
max
-10
°)
-19-
Setting of TRIP, Q
min
or Imp
822X/824X
-20-
PTC warning
-21-
Apparent motor current (C054) < current
threshold (C156)
-22-
Apparent motor current (C054) < current
threshold (C156) and
f
d
> Q
min
threshold
-23-
Apparent motor current (C054) < threshold
(C156) and input of ramp function generator
= output of ramp function generator
822X/824X
-24-
Warning motor phase failure
-25-
f
d
(C050) < f
dmin
(C010)
C114
¿ Signal level
digital inputs
-0-
E4
E3
E2
E1
-0-
0
0
0
0
-1-
0
0
0
1
-2-
0
0
1
0
-3-
0
0
1
1
-4-
0
1
0
0
-5-
0
1
0
1
-6-
0
1
1
0
-7-
0
1
1
1
-8-
1
0
0
0
-9-
1
0
0
1
-10-
1
0
1
0
-11-
1
0
1
1
-12-
1
1
0
0
-13-
1
1
0
1
-14-
1
1
1
0
-15-
1
1
1
1
0: Ex is not inverted
1: Ex is inverted