4.2.3.2

Assignment of the control terminals

62

7

8

9

K11

K12

K14

20

28

E1

E2

E3

E4

39

K21

K22

K24

hPRKMMOT

Protection against contact
The control terminals have a basic isolation (double insulating

distance). The protection against contact is ensured without any

additional measures.
Protection against polarity reversal
The protection against polarity reversal prevents from the wrong

connection of the internal control inputs. It is however possible to

overcome the protection against polarity reversal by applying great

force. The controller cannot be enabled then.
Motor temperature monitoring
The connections of the motor-temperature monitoring (T1, T2) are
next to the connection terminals U, V, W.

cfd QJT

mçëáíáçå зС нЬЙ Езенкзд нЙкгбе~дл

Terminal

Use
(Factory setting is printed in bold)

Level

Data

Analog

7

GND 1

g

inputs

8

Setpoint input,

reference:

Terminal 7
(0 to 10V)

6

4

2

5

3

1

5 - 6
5 - 6
3 - 4
1 - 2

0 to 20 mA
4 to 20 mA
0 to 5 V
0 to 10 V

Resolution: 10 bit
Linearity error:

±0.5 %

Temperature fault: 0.3 % (0...+40

°C)

Input resistance
Voltage signal: > 100 kΩ

Jumper

Voltage signal: > 100 kΩ
Current signal: 250 Ω

9

Supply for setpoint potentiometer

5.2V / 6mA

Analog
output

62

Analog output, reference: terminal 7
0 ... 6V (changes possible under C108)

0... 10 V / 2

mA

Resolution: 10 bit

Digital

inputs

20

Voltage supply for digital inputs
15 V/20 mA

p

28

Controller enable

HIGH

HIGH:

12 V ... 30 V

E4

CW rotation/
CCW rotation (CW/CCW)

CW: LOW
CCW: HIGH

LOW:

0 V ... 3 V

E3

DC-injection brake

HIGH

E2

JOG frequencies

Binary code

E1

q

20Hz, 30Hz, 40Hz

y

39

GND 2 (reference for external voltages)

Monitoring T1

Motore-temperature monitoring
(PTC thermistor/thermal contact)

If not used: set parameter C119 = -0-!

T2

Motore-temperature monitoring
(PTC thermistor/thermal contact)

Terminal

Use
(Factory setting is printed in bold)

Relay position (switched)

Data

Relay

output K1

K 11

Relay output normally-closed contact
(TRIP)

opened

24 V AC / 3,0 A or
60 V DC / 0.5 A

p

K 12

Relay mid-position contact

K 14

Relay output normally-open contact
(TRIP)

closed

Relay

output K2

K 21

Relay output normally-closed contact
(Ready for operation)

opened

250 V AC / 3,0A or
60 V DC / 0.5A

p

K 22

Relay mid-position contact

250 V AC / 3,0A or
60 V DC / 0.5A

K 24

Relay output normally-open contact
(Ready for operation)

closed

250 V AC / 3,0A or
60 V DC / 0.5A