Optimisation of motor-current control

Codes required

Code

Name

Possible settings

IMPORTANT

Lenze

Selection

Info

C015 V/f rated frequency

50.00 7.50

{0.02Hz}

960.00

C021 Slip compensation

0

-50.0

{0.1 %}

50.0

C088 Rated motor current

*

0.0 ... 2.0

¡

rated output current

* depends on

the unit

Input only necessary

when motors not

C091 Motor cos

j

*

0.4

{0.1}

1.0

the unit

when motors not

adapted.

Setting sequence

D

Drives with matching 4 pole standard motors 230/400 V in star connection do not need to be

adapted.After having started the drive, the controller itself detects all further motor data.

D

The following drives can be optimized by entering the nameplate data ”rated motor current” and

”cos

j” under C088 or C091:

- Motor one power class smaller than the motor assigned to the controller.
- Motor one or two power classes smaller than the motor assigned to the controller.
- Drives with 2, 6, 8, 10 and 12 pole standard motors.
- Drives with special motors.

D

With the slip compensation C021, you can optimize the ”sensorless speed control” for your

application.

1.If necessary,

select C014 = -4-.

(factory setting)

2.Select V/f-rated frequency

(C015).

Motor voltage

Motor

connection

C015

(

)

220/380 V

Y

52,6 Hz

230/400 V, 265/460 V, 280/480 V

Y

50 Hz

220/380 V, 230/400 V, 265/460 V, 280/480 V

D

87 Hz

380/660 V

D

52,6 Hz

400/690 V

D

50 Hz

3.If necessary, enter the motor

data of unadapted motors
(C088, C091).

4.Set slip compensation

Rough setting by means of the motor data:

p

p

(C021):

л =

е

клуе

− е

к

е

клуе

⋅ NMMB

е

клуе

=

С

Зк

⋅ SM

é

s

Slip constant (C021)

n

rsyn

synchronous motor speed [min

-1

]

n

r

rated speed to motor nameplate [min

-1

]

f

dr

rated frequency to motor nameplate [Hz]

p

Number of pole pairs

Precise setting:
Change C021 under constant load until the speed is near the synchronous speed.
If C021 is set to too high values, the drive may become instable (overcompensation).

Important

D

The change from V/f-characteristic control to motor-current control should only be carried out

when the controller is inhibited.

D

The idle current of the motor (magnetizing current) must not exceed the rated current of the

controller.

D

With very small friction values it is possible that an angle offset of up to 180

° occurs when

enabling the controller.