Configuration – Lenze 8240 HVAC Series User Manual
Page 68
![background image](/manuals/566193/68/background.png)
Configuration
7-4
UOOuhäáã~_^NMMO
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C007
¿
(continued)
Terminal
configuration
-0-
E4
E3
E2
E1
-11-
CW/CCW DC brake UP
DOWN
-12-
CW/CCW PAR
UP
DOWN
-13-
CW/CCW QSP
UP
DOWN
-14-
CCW/QSP CW/QSP
DC brake JOG1
-15-
CCW/QSP CW/QSP
PAR
JOG1
-16-
CCW/QSP CW/QSP
JOG1/2/3
-17-
CCW/QSP CW/QSP
PAR
DC brake
-18-
CCW/QSP CW/QSP
PAR
Trip set
-19-
CCW/QSP CW/QSP
DC brake Trip set
-20-
CCW/QSP CW/QSP
Trip set
JOG1
-21-
CCW/QSP CW/QSP
UP
DOWN
-22-
CCW/QSP CW/QSP
UP
JOG1
-23-
M/R
CW/CCW UP
DOWN
-24-
M/R
PAR
UP
DOWN
-25-
M/R
DC brake UP
DOWN
-26-
M/R
JOG1
UP
DOWN
-27-
M/R Trip set
UP
DOWN
-28-
JOG1/2/3
I-OFF
D/F
-29-
JOG1
DC brake
I-OFF
D/F
-30-
JOG1
QSP
I-OFF
D/F
-31-
DC brake
QSP
I-OFF
D/F
-32-
Trip set QSP
I-OFF
D/F
-33-
QSPPAR
I-OFF
D/F
-34-
CW/QSPCCW/QSP
I-OFF
D/F
-35-
JOG1/2/3
PAR
D/F
-36-
DC brake
QSP
PAR
D/F
-37-
JOG1
QSP
PAR
D/F
-38-
JOG1
PAR
Trip set
D/F
-39-
JOG1/2/3
Trip set
D/F
-40-
JOG1
QSP
Trip set
D/F
-41-
JOG1
DC brake Trip set
D/F
-42-
QSP
DC brake Trip set
D/F
-43-
CW/CCW QSP
Trip set
D/F
-44-
UP
DOWN
PAR
D/F
-45-
CW/CCW QSP
PAR
D/F
-46-
M/R
PAR
QSP
JOG1
-47-
CW/QSP
CCW/QSP M/R
JOG1
-48-
INFL_0
DC brake I-OFF
D/F
-49-
INFL_0
JOG1
QSP
D/F
-50-
INFL_0
JOG1
I-OFF
D/F
-51-
DC brake PAR
I-OFF
D/F
D
Trip-Set =
External fault
D
UP/DOWN =
Motor
potentiometer
functions
D
M/R =
Manual/Remote
changeover
D
I-OFF =
Reset I-component
of the PID
controller
D
D/F =
Digital frequency
input 0 - 10 kHz
D
INFL_0 =
Set influence of the
PID controller to 0
When changing
between the
parameter sets via
terminal, the
corresponding
terminal must be
assigned with PAR in
both parameter sets.