Configuration
7-3
UOOuhäáã~_^NMMO
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C003
¿ Save parameter
set
-1-
-0-
Data will not be saved on EEPROM; all data
will be lost when switching off the mains
-1-
Data will be saved on EEPROM; setting
when switching on the mains
-0- only valid for
C010, C011, C012,
C013, C037, C038,
C105, C181 and
C182
C004
¿ Switch-on display
-0-
-0-
Field frequency f
d
-1-
Unit load
-2-
Motor current
C005
¿ Configuration
-0-
-0-
Operation with open-loop control via
terminal 8
-1-
Operation with open-loop control via
terminal 8 with setpoint summation via
frequency input E1
-2-
Operation with open-loop control via
frequency input E1 with setpoint
summation via terminal 8
-3-
Operation with open-loop control via
frequency input E1 with torque limitation
via terminal 8
-4-
Torque selection via terminal 8 with speed
limitation via f
dmax
(C011)
-5-
Torque selection via terminal 8 with speed
limitation via frequency input E1
-6-
Operation with closed-loop control; setpoint
via terminal 8 with digital frequency
feedback via terminal E1
-7-
Operation with closed-loop control, setpoint
via frequency input E1 with analog
feedback via terminal 8
Selections -4- and
-5- are only
permitted for
motor-current control
(C014 = 4) and with
activated flying
restart circuit
(C142 = 2, 3).
C007
¿ Terminal
configuration
-0-
E4
E3
E2
E1
-0-
CW/CCW DC brake JOG1/2/3
-1-
CW/CCW PAR
JOG1/2/3
-2-
CW/CCW QSP
JOG1/2/3
-3-
CW/CCW PAR
DC brake
JOG1
-4-
CW/CCW QSP
PAR
JOG1
-5-
CW/CCW DC brake Trip set
JOG1
-6-
CW/CCW PAR
Trip set
JOG1
-7-
CW/CCW PAR DC brake
Trip set
-8-
CW/CCW QSP
PAR
Trip set
-9-
CW/CCW QSP
Trip set
JOG1
-10-
CW/CCW Trip set
UP
DOWN
D
CW =
CW rotation
D
CCW =
CCW rotation
D
DC brake =
DC injection brake
D
PAR =
Change of
parameter sets
D
JOG =
JOG frequency
D
QSP =
Quick stop